INSPECTING THE MODULE
5.1 To make sure your S2000-SP1 module keeps proper operability, it must be inspected by
a competent specialist at least on receipt and annually.
5.2 Inspect the module at following ambient conditions:
The relative humidity 45% through 80%;
–
The ambient temperature 15°C through 35°C;
–
The atmospheric pressure 630 mm Hg through 800 mm Hg.
–
5.3 While inspecting the module, always shut off the module power before connecting and
disconnecting its external circuits.
5.4 Full inspection of the module comprises inspecting the module's operability and testing the
module in its self-diagnostic mode.
5.5 Inspecting Operability of the Module
5.5.1 To inspect module's operability, use an S2000M fire and
alarm console. Connect the module's RS-485 circuits and power
circuits to the relevant terminals of the console (see the S2000M
manual for detailed instructions).
5.5.2 Power on the module and the console.
5.5.3 The module's READY indicator shall be lit steady in green
within 5 s.
5.5.4 Within a minute since powering on the console it shall
display a message about detecting a device with the network
address assigned to the module (factory value of the module
address is 127). Figure 5 shows the display of the S2000M
console with the relevant message.
5.5.5 If several messages accumulated by the module have been received by the console,
you can browse them by the arrow buttons «◄» and «►» on the S2000M.
5.6 Testing the S2000-SP1 in the Self-Diagnostic Mode
Before turning on the self-diagnostic mode of the module, detach its executive circuits
which must not be activated on testing!
5.6.1 To activate the self-diagnostic mode of the module, open its front cover and press the
tamper switch on the PCB in SSSL pattern, where "S" ("short") stands for holding the tamper
switch pressed for 0.1 s to 0.5 s while "L" ("long") stands for holding the tamper switch
pressed for at least 1.5 s. Pauses between pressings should be 0.1 to 0.7 s.
5.6.2 If the module operates correctly, its READY indicator shall flash five times per second
while relays "1" to "4" shall be activated one-by-one for a short time.
www.bolid.com
S2000-SP1 ver.1.56 INSTALLATION MANUAL rev.0
Figure 5