Akytec SMI2 Manuel de l'utilisateur - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} Akytec SMI2. Akytec SMI2 12 pages. Rs485 display

Carefully position the supplied gasket on the display rear surface. Insert the cylindrical part
of the device into the borehole and tighten the nut from the rear side of the switch panel.
Connect the device to the auxiliary voltage and signal cables in accordance with Appendix B.
The factory settings can be changed before assembly if necessary (see Appendix D.3). For
this purpose the device must be connected to the RS485 interface of the programming
device (PC) and to the auxiliary power supply. For further details see 5.3.
5.2

Programming

The display may only be programmed in the RS485 network with the communications
protocol Modbus RTU/ASCII or akYtec in the slave mode. The protocol type is specified in
the parameter Protocol type (t.Pro) (see Table D3).
The configuration software „Konfigurator SMI2" allows to configure the device via the akYtec
protocol. The CD with the configuration software is supplied with the device. Further steps
are given in 5.3.
The parameters are divided into two main groups: the configuration parameters and
transmitted data.
The configuration parameters are device information, network parameters and operating
parameters. The latter determine how the device processes the received information.
The configuration parameters are constants and are saved in the permanent memory (Table
D3).
The transmitted data are variable data exchanged between the master and slave. These are
not saved (Table D4).
Each parameter has a name consisting of Latin letters (up to four), which can be separated
by points.
5.3

Configuration

Required steps for configuration:
Connect a USB/RS485 or RS232/RS485 converter (not supplied) to the PC
Connect the display to the 24 V DC power supply and to the RS485 terminals of the
converter according to Fig. B1
Switch on auxiliary voltage
Install and start SMI2 configuration software
In the menu select "Device -> Port configuration..." and set the parameters to the device
factory settings (see 5.5)
Check connection with the device (menu "Device -> Check connection")
A new device can be configured immediately.
As soon as the parameter Protocol type (t.Pro) is changed and saved, the communication
with the device is interrupted. To enable the SMI2 configuration software to communicate
with the device again, the "Factory settings" mode must be temporarily activated.
5.4

Configuration check

After the RESET button is pressed for a short time, the display extinguishes for 3 seconds,
and all current parameters of the device are then displayed.
The parameters are presented in the following way:
Parameter name (2 seconds),
Parameter value (2 seconds),
Pause (1 second),
Next parameter.
The display order corresponds to the register number from the Table D3, column 2.
The RESET button must be pressed for a short time again to terminate the display of
parameters.