DOTECH FX3DH Series Manuel - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} DOTECH FX3DH Series. DOTECH FX3DH Series 4 pages. Digital temp. & humidity controller
Également pour DOTECH FX3DH Series : Manuel de l'utilisateur (9 pages)

DOTECH FX3DH Series Manuel
Setting Method of control mode
※ According to user's setup, FX3DH is able to use humidity only or temperature
only or for both temperature and humidity. Please use after you setup the
parameter of sensor input of setting 2 group.
I N
Setup sensor input of setting 2 group.
Use for humidity only
H
Use for temperature only
T
Use for humidity and temperature control
HT
(Output1: humidity control, output2: temperature control)
Humidity and temperature are displayed by every
2.5 sec. interval in shifts.
Use for humidity control and temperature display.
HTD
Humidity and temperature are displayed by every
2.5 sec. interval in shifts.
Simple Trouble Check Point
※ FX3DH controls by measured value which is detected by sensor.
If sensor fault alarm occurred as following, please check wiring with sensor
Humidity Sensor
HOP
Open Wire
Humidity Sensor
H S T
Short Circuit
Minimum range
HLL
for Humidity use
Maximum range
HHH
for Humidity use
If the stored value is changed randomly, please re-setup after
SYS
parameter initialization.
※ In case of the above-mentioned error, it will be normally operated with cancelling error
status if the reason of error is solved.
Temperature Setting Group
Display Current Temp.
Run Mode
The set point is indicated by flickering at every
Push for
0.5 seconds intervals and this set point can be
3 sec.
established by using the ▲ key or ▼ key.
After changing set point, it displays the current temp.
If there's no input made for a period of 60 seconds during the setting,
then it returns back to the run mode automatically.
When it use for Humidity & Temp. control
(Apply HTX20-FTS-502 Temp. & Humidity sensor)
※ Set sensor input setting(IN) of setting 2 group to HT.
HTX20-FTS-502
+5V
RH : 10~95%RH, 1.2~3.5V
RH
T : NTC5K
GND
TH
RH & Temp Sensor
TH
dotech,inc
When it use for Humidity control
※ Set sensor input setting(IN) of setting 2 group to H.
HTX20-FTS-502
+5V
RH : 10~95%RH, 1.2~3.5V
RH
T : NTC5K
GND
TH
RH & Temp Sensor
TH
dotech,inc
When it use for Humidity control
※ Set sensor input setting(IN) of setting 2 group to H.
When it use for temperature control
※ Set sensor input setting(IN) of setting 2 group to T.
Temperature Sensor
T OP
Open Wire
Temperature Sensor
TST
Short Circuit
Minimum range
T LL
for Temperature use
maximum range
T HH
for Temperature use
Output #1 setup value
Set output #1 setup value.
Output #2 setup value
Set output #2 setup value.
RED
YELLOW
BLACK
WHITE
BLUE
(Apply HTX20-FTS-502 Humidity sensor)
RED
YELLOW
BLACK
(Apply HTX3515 Humidity sensor)
RED
WHITE
BLACK
(Apply DPR-TH1-ET Temp. sensor)
Deviation Control(TP mode)
when TP mode is P
dF
St
dF
OUTPUT ON
Dehumidification
(Cooling)Control
OUTPUT ON
Humidification
(Heating)Control
Distinguishment between Temperature and Humidity.
OUT1
OUT2
Setting 1 Group
Display
Run Mode
Current Temp.
Push for 3 sec.
Push for
Select Control Type #1
3 sec.
dF/2
PV
St
dF/2
OUTPUT ON
Dehumidification
(Cooling)Control
Humidification
(Heating)Control
In the case of temperature display,
℃ unit is displayed.
In the case of Humidity display,
unit will not be displayed.
Set control function of
control output #1.
No use output function
(Use display mode only.)
Use cooling control only
(Use OVER temperature sensing only.)
Use heating control only
(Use UNDER temperature sensing only.)
Deviation High Limit Alarm
A L 1
Output is ON when the deviation between
PV value and SV value is higher than setup
value of deviation temperature.
Deviation Low Limit Alarm
AL2
Output is ON when the deviation between
PV value and SV value is lower than setup
value of deviation temperature.
Deviation High & Low Limit Alarm
AL3
Output is ON when the deviation between
PV value and SV value is higher or lower
than setup value of deviation temperature.
Deviation High & Low Limit Reverse Alarm
Output is OFF when the deviation between
AL4
PV value and SV value is higher or lower
than setup value of deviation temperature.
Absolute Value High Limit Alarm
AL5
Output is ON when PV value is higher than or
equal as alarm temperature setup value.
Absolute Value Low Limit Alarm
AL6
Output is ON when PV value is lower than or
equal as alarm temperature setup value.
Sensor Open Wire Alarm
SBA
Output is ON when sensor wire is opened.
Control Deviation Value #1
Set control sensitivity of control output #1.
Setting Range 0 ~ 19.9
Select deviation type #1
+ Deviation control
± Deviation control
e.g)Condition : Cooling mode,
setting temp.10.0 ℃ , deviation 1.0 ℃
+Deviation control : ON at 11.0 ℃ , OFF at 10.0 ℃.
±Deviation control : ON at 10.5 ℃ , OFF at 9.5 ℃.
ON Delay Time #1
Output after delaying during setting
delay time in case of control
output #1 ON.
Minimum OFF Time #1
No output within Min. OFF time
after control output #1 OFF.
Minimum ON Time #1
Maintain ON in spite of OFF
condition during Min. ON time
after ON.
Output #1 at Sensor Error
Set output #1 when sensor is
disconnected or shorted.
e.g) In case of setting as ON,
output #1 is ON when error occurs.
Alarm Deviation Value
Set control sensibility of alarm output.
Setup range is 0~99.9
Alarm Option
General alarm
Standard alarm operation
ALA
without option
Maintain alarm
Maintain output ON after
ALB
alarm occurs
Standby alarm
No output at initial operation
ALC
(until achieve the 1st setup value)
Maintain & standby alarm
Execute both ALD & ALC
ALD
at the same time
Max. Setup Value by User
Input max. value settable by user
Possible to set until 100.
Min. Setup Value by User
Input min. value settable by user
Possible to set until 0.
Manual Output Mode Output #1
(-R4 Model)
OFF : Output by temp.
ON : Output by
MV1
Manual Output Value Output #1
(-R4 Model)
Output continuously regardless setup
temp. if manual output value is ON
when manual output mode is ON.
when TP mode is PN
PV
OUTPUT ON
Select Control
Type #2
UH2
UL2
2