Electrex FEMTO 96 Manuel d'installation - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Electrex FEMTO 96. Electrex FEMTO 96 4 pages.
Également pour Electrex FEMTO 96 : Manuel d'installation (4 pages)
Note n.1
3PH-3W-2CT 2 phases 3 wires, triangle
3PH-4W
3 phases 4 wires, Star
2PH-2W
2 phases 2 wires, biphase
1PH-2W
1 phase 2 wires, monophase
Note n.2
POWERS
Integration time of the average value (AVG) and peak value (MD) for
power (from 1 to 60 minutes)
CURRENTS
Integration time of the average value (AVG) and peak value (MD) for
current (from 1 to 60 minutes)
Note n.3
Normal
Classic Alarm with reference to a fi xed threshold or to maximum and
minimum delay and applicable hysteresis. "AVG" parameter is not used.
1-OF-3
Consider also the 2 following registers of the selected one in "MEAS" .
Works on a fi xed max or min threshold with delay and applicable hysteresis.
If one of the three register exceed the threshold the alarm goes on. "AVG"
parameter is not used.
3-OF-3
Consider also the 2 following registers of the selected one in "MEAS".
Works on a fi xed max or min threshold with delay and applicable hysteresis.
When all the three register exceed the threshold the alarm goes on. "AVG"
parameter is not used.
DERIV
"THRE" parameter becomes a % value, "AVG" parameter is used. The
instant value applied to the alarm on "MEAS" is compared with its value
mediated obtained on the basis of the time set on "AVG". When the
instantaneous value combined alarm differs in more (setting "Max") or less
(setting "MIN") from the average value (" AVG ") of the percentage set on
"THRE" the alarm goes on. With delay and applicable hysteresis.
UNBAL
Consider also the 2 following registers of the selected one in "MEAS".
"THRE" parameter becomes a % value. Alarm goes on when one of the
three register is different from the percentage set on "THRE" comply with
the higher value of the three read register if "MAX" is set on "TYPE", or
comply with the lower value of the three register if "MIN" is set on "TYPE"
With delay and applicable hysteresis.
Note n.4
MAX
Alarm setting in excess compared with the established conditions.
With the exception of "UNBAL".
MIN
Alarm setting in decrease compared with the established conditions.
With the exception of "UNBAL"
Note n.5
MEAS
indicates which register (and thus measure) the alarm is related.
See table n.1 input register.
THRE
Alarm threshold in absolute value, with the exception made for "DERIV"
and "UNBAL" in which the value inserted becomes a percentage.
Note n.6
AVG
Parameter to be used only in "DERIV" mode. Is the duration of the refe-
rence (in seconds) used to create a reference value for the istantaneous
readings.
Note n.7
NORMAL
Physical output of the alarm excited during the duration of the alarm. It
restores automatically
HOLD
Output remains excited until manual reset made via Modbus
PULSE-L
Output generate a 500ms impulse when the alarm goes on.
PULSE-S
Output generate a 100ms impulse when the alarm goes on.
Note n.8
PULSE
Enables exit function as impulsive
ALARM
Enables exit function as alarm
REMOTE
Enables function output via protocol Modbus
NO
Normally open
NC
Normally closed
Note n.9
P-IMP
Imported Active Power (Energy)
QL-IMP
Imported Reactive Inductive Power (Energy)
QC-IMP
Imported Reactive Capacitive Power (Energy)
S-IMP
Imported Apparent Power (Energy)
P-EXP
Exported Active Power (Energy)
QL-EXP
Exported Reactive Inductive Power (Energy)
QC-EXP
Exported Reactive Capacitive Power (Energy)
S-EXP
Exported Apparent Power (Energy)
Note n.10
YES
Referred to CT primary
NO
Referred to CT secondary
Note n.11
ALLARME 1 Alarm related to the physical output: DIGITAL OUT 1 (DO1, terminal 8)
ALLARME 2 Alarm related to the physical output: DIGITAL OUT 2 (DO2, terminal 9)
ALLARME 3 Only MODBUS alarm
ALLARME 4 Only MODBUS alarm
MESSAGE "CFG ERROR"
During the set up operation a "CFG ERROR" message could appear. This means
that some wrong parameters are typed. To restore the factory default settings use the
following procedure (RESTORE FACTORY SETTING):
CFG ERROR
Once this procedure is done the meter is confi gured with its factory default settings.
Stored data will remain after the restore operation.
RESTORE
FACTORY SETTINGS
YES
DIGITAL INPUTS AND OUTPUTS CONNECTION
(only for the version PFA6C11-12)
+
20
DI (-)
19
DI (+)
19
AUX
!
IN/OUT
Digital Inputs
Supply voltage (external):
from 10 to 30
Vdc
Current consumption:
from 2 to 10mA
Max. count frequency
10 or 100Hz
N.B. For gas meters a galvanic separation is
needed per ATEX standards
INPUT & OUTPUTS CONNECTION EXAMPLE
U1 U2 U3
N
17
VOLTAGE INPUT POWER
I1
I2
I3
RS-485
S1 S2 S1 S2 S1 S2 A B
FROM:
- TRANSDUCER WITH CONTACT CLEAN
- GME
- STATE ON-OFF
- STATE ALARMS
U1 U2 U3
N
VOLTAGE INPUT POWER
I1
I2
I3
S1 S2 S1 S2 S1 S2 A B
ALARM SET UP EXAMPLE
To ensure that the exit "DIGITAL OUT 1" remain excited for the alarm duration (latching)
when average active power (MEAS 344) exceeds the value of 100 kW, hysteresis, 5%
and latency of 5 seconds set the parameters such as table:
MODE (note n.2)
TYPE (note n.3)
ALARM 1 / A
MEAS (note n.4)
THRE (note n.4)
HYST
DELAY
ALARM 1 / B
AVG (note n.5)
OUT (note n.6)
MODE
DIGITAL OUT 1
POLARITY
To ensure that the exit "DIGITAL OUT 2" remain excited for the alarm duration (latching)
when average active power (MEAS 344) goes down the value of 90 kW, hysteresis, 5%
and latency of 5 seconds set the parameters such as table:
MODE (note n.2)
TYPE (note n.3)
ALARM 2 / A
MEAS (note n.4)
THRE (note n.4)
HYST
DELAY
ALARM 2 / B
AVG (note n.5)
OUT (note n.6)
MODE
DIGITAL OUT 2
POLARITY
-
12
DO2
11
20
DO1
10
Common
Digital outputs (optocoupled NPN
transistor type for DIN 43864)
Maximum applicable voltage:
Maximum switchable current:
Out PLC
Common
(+)
(-)
Es. PLC
18
19
20
AUX
Es.
Input M8 Supervisor
AUX
1 2 C
3 4
C
10 11 12
(-) (+) (+)
NC
NC
17
18
19
20
C
C
230 Vac
AUX
NO
NO
Power
R
R
e
e
Supply
l
l
a
a
y
y
Max
27 Vdc
27 mA
RS-485
AUX
10 11 12
(-)
(+)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
PULSE, ALARM, REMOTE
NO, NC
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
PULSE, ALARM, REMOTE
NO, NC
AUX
!
IN/OUT
10
11
12
C
1
2
27 Vdc
27 mA
NORMAL
MAX
344
100000
5
5
1
NORMAL
ALARM
NO
NORMAL
MIN
344
90000
5
5
1
NORMAL
ALARM
NO