Electrex ATTO D4 Instructions d'installation

Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} Electrex ATTO D4. Electrex ATTO D4 4 pages. Transducer / analyzer

ATTO D4
INSTALLATION INSTRUCTIONS
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written authorization,
except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for a
period of 24 months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence of a
negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. The
transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warranty
terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010 class 2
standards for operating voltages up to 250 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
!
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument
must be taken out of service and precautions taken againstits accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger of
death.
• During normal operation dangerous voltages can occur on instrument terminals and
on voltage and current transformers. Energized voltage and current transformers
may generate lethal voltages. Follow carefully the standard safety precautions while
carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where the
display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions.
The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by the
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the
instrument.
• The instrument is equipped with PTC current limiting device but a suitable external
protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be powered by
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage
to the instrument.
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.

DECLARATION OF CONFORMITY

Akse hereby declares that its range of products complies with the following directives EMC
2014/30/EU, 2014/35/EU and complies with the following product's standard CEI EN
61326 - Ed. 2.0 (2012) – IEC 61326 - Ed. 2.0 (2012), CEI EN 61010- Ed. 3 (2010) – IEC
61010- Ed. 3 (2010). The product has been tested in the typical wiring confi guration and
with peripherals conforming to the EMC directive and the LV directive.
The instrument is programmed with the following default values:
PAGE
MENU DISPLAYED
PASSWORD
RS485
RS 485 ADDRESS
Comm. Speed
Data Bit
Parity
Bit of stop
NETWORK
Type (note n.1)
Export
CT
VT
AVG-MD TIME (note n.2)
POWERS
CURRENTS
ALARM 1 / A (note n.11)
MODE (note n.3)
TYPE (note n.4)
MEAS (note n.5)
THRE (note n.5)
ALARM 1 / B
HYST
DELAY
AVG (note n.6)
OUT (note n.7)
ALARM 2 / A (note n.11)
MODE (note n.3)
TYPE (note n.4)
MEAS (note n.5)
THRE (note n.5)
ALARM 2 / B
HYST
DELAY
AVG (note n.6)
OUT (note n.7)
ALARM 3 / A (note n.11)
MODE (note n.3)
TYPE (note n.4)
MEAS (note n.5)
THRE (note n.5)
ALARM 3 / B
HYST
DELAY
AVG (note n.6)
OUT (note n.7)
ALARM 4 / A (note n.11)
MODE (note n.3)
TYPE (note n.4)
MEAS (note n.5)
THRE (note n.5)
ALARM 4 / B
HYST
DELAY
AVG (note n.6)
OUT (note n.7)
DIGITAL OUT 1 (note n.8)
MODE
POLARITY
PULSE OUT 1
MEAS (note n.9)
PRIMARY (note n.10)
WEIGHT
WIDTH
DIGITAL OUT 2 (note n.8)
MODE
POLARITY
PULSE OUT 2
MEAS (note n.9)
PRIMARY (note n.10)
WEIGHT
WIDTH
MECHANICAL CHARACTERISTICS
Enclosure
Self-extinguishing plastic material class V0
Protection degree
IP40 on front panel
Dimensions
70 x 90 x 58 mm (4 DIN modules)
VOLTAGE INPUT
Direct
Up to 300 Vrms phase-neutral or 519 Vrms phase to phase
With external PT(VT)
Primary: programmable (max. 400 kV)
Secondary: programmable (max. 300 V)
Overload: 900 Vrms phase to phase for 1 sec
Power supply
230/240Vac +/- 10% 50/60Hz
Self consumption
< 3VA
MODELS
PFA7411-02
ATTO D4 RS485 230-240V
TRANSDUCER / ANALYZER
PFA7411-12
ATTO D4 RS485 230-240V 1DI 2DO
TRANSDUCER / ANALYZER
AVAILABLE PARAMETERS
0000 ... 9999
1 ... 247
2400, 4800, 9600, 19200, 38400
7 o 8
N = no parity, E =even parity, O = odd parity
1 o 2
3PH-3W-2CT, 3PH-4W, 2PH-2W, 1PH-2W
NO, YES
10000/1 o 5
400000/300
1...60 (minutes)
1...60 (minutes)
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL
MAX, MIN
Controlled measure. See table n.1 for register
selection
Threshold value
1...100 (%)
1...99 (seconds)
1...99 (seconds)
Normal, Hold, Pulse-L, Pulse-S
PULSE, ALARM, REMOTE
NO, NC
P-IMP, QL-IMP, QC-IMP, S-IMP, P-EXP,
QL-EXP, QC-EXP, S-EXP
YES, NO
1...100000000 (Wh/100)
50ms...1S
PULSE, ALARM, REMOTE
NO, NC
P-IMP, QL-IMP, QC-IMP, S-IMP, P-EXP,
QL-EXP, QC-EXP, S-EXP
YES, NO
1...100000000 (Wh/100)
50ms...1S
DEFAULT
0000
27
38400
8
N
2
3PH-4W
NO
5/5
1/1
15
8
NORMAL
MIN
200
0
1
1
1
NORMAL
NORMAL
MIN
200
0
1
1
1
NORMAL
NORMAL
MIN
200
0
1
1
1
NORMAL
NORMAL
MIN
200
0
1
1
1
NORMAL
PULSE
NO
P-IMP
YES
100000
500
PULSE
NO
QL-IMP
YES
100000
500