Amphenol Wilcoxon TN14 Dépannage des installations - Page 2
Parcourez en ligne ou téléchargez le pdf Dépannage des installations pour {nom_de_la_catégorie} Amphenol Wilcoxon TN14. Amphenol Wilcoxon TN14 7 pages. Accelerometer
Figure 1 is a diagram representing the performance
of the circuit. The line represented by "Instrument
Power" and BOV is one conductor that has two
functions. So even though the power supply is pro-
viding a higher input voltage, the BOV is the mea-
sured output voltage level on the cable connecting
the accelerometer to the data collector or analyzer.
The BOV carries the dynamic vibration signal to the
analyzer. The AC signal swings high and low from
the BOV level and is limited by the power supply
level and ground. For example, if the power supply
level is 24 volts, the swing of the AC signal would
be limited to no more than 24 volts and no less than
ground (0 volts). These are theoretical limits. In re-
ality, the limits to this swing occur at about 1.5 volts
above ground and about 1.5 volts below the power
supply level, as shown in figure 2.
Most portable data collectors and online systems
supply 24 volts to the sensor. The sensor should
have a nominal BOV of approximately one half of
the power supply voltage, to maximize the amount
of swing in the positive and negative directions.
Most two-wire sensors produce an 8 to 14 volt bias.
When the signal amplitude runs into the supply voltage or ground, clipping occurs. Clipping the vibration signal
distorts the waveform. In other words, a clipped signal is no longer a true analog representation of the vibration
the sensor is attempting to measure.
Measuring the BOV
The constant current diode (CCD) limits the current supplied to the sensor. It provides a constant current to the
sensor regardless of the supply voltage because the use of unlimited power supply current will damage most
internally amplified sensors. For this reason, most commercially available data collectors and vibration moni-
tors have power supply circuits that include a CCD to regulate the power supplied to the sensor.
Figure 3: Schematic of a sensor power
Figure 3: Schematic of a sensor power supply
supply containing a CCD
Figure 1: Sensor amplifier
Figure 1: Sensor amplifier circuits
circuit
Figure 2: AC signal limits
Figure 2: AC signal limits
Most battery power supplies contain a 2 mA CCD to ensure
long battery life. Line powered supplies (where power con-
sumption is not a concern) should contain 6 to 10 mA CCDs.
This offers the ability to drive long cables. For operation above
100° C, it is best to limit the current to less than 6 mA to re-
duce self heating. Most data collectors supply 2 mA of cur-
rent to the sensor; most online systems supply 4 to 6 mA. If a
power supply that is not current limited is used, a CCD should
be placed in series with the voltage output of the supply. En-
sure that proper diode polarity is observed. If a current limited
power supply is probed with a voltmeter the supply voltage will
be measured before the CCD. The bias voltage will be mea-
sured on the side of the CCD connected to the sensor. Figure
3 shows a schematic of a sensor power supply containing a
fixed CCD between 2 and 10 mA.
Page 2