Amphenol Telect 009-7001-0104B-TFD Manuel d'installation - Page 10

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Amphenol Telect 009-7001-0104B-TFD. Amphenol Telect 009-7001-0104B-TFD 15 pages. High-current demarcation panel

13. Clean the terminals with a nonabrasive,
nonmetallic pad.
14. If required, lightly coat antioxidant on lugs
and input terminals and then connect lugs
to input terminals on back of panel. Tighten
lugs to 36 in/lb. (4 N•m).
15. Before installing breakers and output wiring,
turn power on to verify input power and
indicators:
Verify input voltage and polarity
Whenever power is supplied, expect the
corresponding PWR ON LED to light
16. For output wiring, repeat steps 8 through 12
for BATT and RTN outputs (crimp output wires
to lugs, clean output terminals and attach lugs
to output terminals). Heat shrink the insulation
onto the lug barrels.
17. Record the circuit assignments on the pull-out
designation card below the alarm display.
18. Attach the plastic covers over all output terminals.
CAUTION! Amphenol Network Solutions recommends
that the individual circuit load not exceed 80% of fuse
capacity (for example, 100A fuse x .80 = 80
max. load).
19. Make sure output devices — devices fed from the
outputs of this demarcation panel — are disabled.
20. With input power on, firmly install each fuse in
panel, as shown in Fig. 9.
Fuses are designed so that the fuses can be
installed in one way only.
21. Check voltage and polarity at output terminals
and equipment ends.
22. Test the alarm card:
High-Current
Demarcation Panel

Fig. 7: Input/Output lug connections

Fig. 8: Power and alarm LEDs on front panel

Fig. 9: Installing fuses

10
Amphenol Network Solutions
All rights reserved. 12.17.19 146161-3
509.926.6000 — amphenol-ns.com.com