Follett Horizon Elite HCD1410R Manuel d'instructions d'installation - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} Follett Horizon Elite HCD1410R. Follett Horizon Elite HCD1410R 13 pages. Remote condensing
Également pour Follett Horizon Elite HCD1410R : Manuel de l'utilisateur (17 pages)

Follett Horizon Elite HCD1410R Manuel d'instructions d'installation
Prior to installation, carefully unpack and inspect the
contents of your condensing unit!
To ensure proper performance, ease of service and warranty coverage, it is critical that you follow
the requirements detailed in this manual. If you cannot meet these requirements or have questions,
call our technical service group at 877.612.5086 for installation support.
2.1
1.1
Condenser Unit Clearances
• Position condenser unit as shown.
Required clearances:
§ Mininum 48" (121.9 cm) front and back
§ Minimum 24" (61.0 cm) left and right
§ Minimum 36" (91.4 cm) above
2
min. 36.00"
(91.4 cm)
24.00"
(61.0 cm)
24.00"
(61.0 cm)
48.00"
(121.9 cm)

Site preparation

air in
48.00"
(121.9 cm)
REMOTE CONDENSING UNIT
1