Specifications:
Models, Sales Order Parts:
Mxp-537 Peripheral Input Card
Applications / Limitations:
Volt free Inputs.
Power Supply must be local to the card.
Earth Monitoring circuit must be disabled if operating on the same ground plane as the Fire Panel
Compatibility:
Mx-5000 Range of Fire Panels
MxP-053 Latch-Stretch Input Module
ExP-005 Switch EOL Module
Requires PC Configuration Tool Version 6.10 Onwards
Requires Firmware Version 1.2 Onwards and Panel Version 50-08 Onwards for access to the
following functionality:
EN54-13 Fault state reporting
Item
Applicable Standards
Operating Temperature
Relative Humidity
PCB
D.C. Supply
Quiescent Current
Max Current
Input Circuits Available
Input (Imax)
Input (V)
Input EOL
Input Active
Max Line Resistance
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
Specification Details
BS EN54-18, BS EN54-13
-5°C to 40°C
95% Non Condensing (maximum)
20mm H x 105mm W x 125mm L, 105 grams
24V (17V to 28V) DC
25mA (10 I/Ps wired with 6K8 EOLs, Vs = 24V)
30mA (10 I/Ps wired with 6K8 EOLs, Vs = 20V)
10, Individually Configurable, Volt Free
30mA, Under Short Circuit
15V ± 5%
6K8
470R
50R