Advanced Mxp-537 Manuel - Page 9
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Advanced Mxp-537. Advanced Mxp-537 12 pages. Peripheral input card
4 General Notes
The DC power to the Mxp-537 card must always be local to the card.
If a mixed peripheral bus is in use, where multiple peripherals of different families share the
same remote power supply, earth monitoring should be performed by the Mxp-537 unless
otherwise indicated.
Only 1 module, per local power supply, should be configured for earth monitoring.
This equipment is constructed with static sensitive components. Observe anti-static precautions
at all times when handling printed circuit boards. Wear an anti-static earth strap connected to
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
panel enclosure earth point.
ELECTROSTATIC
SENSITIVE DEVICES
The unit must be grounded; this is normally achieved via the screw terminals used to secure the
card to the enclosure. Should this not be the case, a dedicated ground must be provided.
Must be
Grounded
www.advancedco.com