2.1 General Configuration Options
The general configuration options provide a set of specific settings to configure the interface to the type of pager
in use and how the pagers are to be notified with information. The default (new) screen is shown below:
2.1.1 General Options
Item
Description
Limit number of
This can be used to prevent a large number of faults, say due to a loop
detector faults
failure, swamping the pager system.
Unticked, the interface will report all faults as they occur.
To restrict the number of possible fault messages, tick the box and then
set the number of fault per hour in the range 1 – 250.
Philips pager
Tick this box if the pager is specifically a Philips pager system. Leave
unticked for all other pager systems.
Monitor Fault Input
Tick this box to utilise the fault input circuit. Leave unticked to ignore the
fault input circuit.
Invert Fault Input
Tick this box to Invert the signal and monitor NO relay contacts.
2.1.2 Retransmission
Item
Description
Retransmit
Unticked, the interface will report all events only once as they occur.
Tick the box to retransmit the events more than once.
Set the retransmit interval in the range 1 – 30 minutes. Set the number of
retransmissions in the range 1 – 255.
NOTE: If the condition persists and if a pager address has been assigned
to the ALL CALL Group, then the interface will send a message to the ALL
CALL pager address after all normal retransmissions have occurred. This
will be sent after the programmed retransmit interval.