Specifications & Ordering:
Models, Sales Order Parts:
Mxp-014: 8 Way Input Card
Mxp-014F: 8 Way Input Card fitted within a Mx-4100/L, Mx-4200, Mx-4400 or Mx-4800 control panel
Applications / Limitations:
All inputs can be individually programmed to any of the specific functions allowed in the control panel
programme: i.e. Fire, fault, pre-alarm, security, record, alarm-1, alarm-2, alarm-3, key-lock, silence, resound,
mute, reset, disable group, control signal and fire evacuate.
Only one 8 Way Input card can be fitted to an Mx-4100/L, Mx-4200 or Mx-4400 control panel.
Up to two 8 Way Input cards can be fitted to an Mx-4800 control panel.
Compatibility:
The Mxp-014 is fully compatible with the following Fire Alarm Control Panels.
Mx-4100/L, Mx-4200, Mx-4400 & Mx-4800
Mounting pillars are provided to mount this card as follows:
Mx-4200, Mx-4400 & Mx-4800 panel chassis
Mx-4100/L on the rear face of the back box.
Item
Specification Details
Switch Inputs
8 normally open inputs. (Can be inverted via software programming for normally closed
operation on an individual basis).
Each input fed from a 24v supply and optically isolated.
On board indication
8 on board Green LED indicators.
LED illuminates when the switch is closed.
Power Supply
24V DC
(E.G. Wired from panel 24V Aux Supply)
Open: – 0mA
Supply Current
Closed: – 2.2mA
Dimensions
55mm x 105mm x 18mm
(H x W x D)
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice