AirStage ABUA14TLAV Manuel d'installation - Page 14
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} AirStage ABUA14TLAV. AirStage ABUA14TLAV 17 pages. Indoor unit
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the remote
controller.
For details, please refer to the remote controller manual.
] 1
7.2. Custom code setting
Use an insulated screwdriver to set the DIP switches.
Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Confusion
Indoor unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2, referring to the Table B.
ON
OFF
sw
sw
1
2
A (Factory setting)
DIP switch SET 3 SW1
DIP switch SET 3 SW2
]
En-13
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
6
2
3
4
5
6
A
B
C
D
E
10
11
12
13
14
CAUTION
Code change
A
B
C
D
A
B
C
D
Dip switch "SET 3"
sw
sw
3
4
Table B
Custom code
B
C
OFF
ON
OFF
OFF
OFF
ON
] 1
7.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
7
7
Function details
F
15
Function
Filter indicator
interval
Filter indicator
action
Horizontal swing
airfl ow direction
Cool air
temperature
trigger
Heat air
temperature
trigger
Auto restart
Cool Air
Prevention
External control
D
ON
Error report
ON
target
Fan setting
when cooling
thermostat OFF
Function
Setting number
Default
number
○
00
Standard
11
01
Longer
02
Shorter
○
00
Enable
01
Disable
13
Display only
on central
02
remote
controller
○
00
Standard
24
01
Left half
02
Right half
○
00
Standard
30
01
Adjust (1)
02
Adjust (2)
○
00
Standard
01
Adjust (1)
31
02
Adjust (2)
03
Adjust (3)
00
Enable
40
○
01
Disable
○
00
Super low
43
Follow the
setting on
01
the remote
controller
○
00
Start/Stop
Emergency
46
01
stop
02
Forced stop
○
00
All
Display only on
47
01
central remote
controller
Follow the
setting on
○
00
the remote
49
controller
01
Stop
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the horizontal swing airfl ow
direction.
(For horizontal swing equipped
models)
Adjust the cool air trigger temperature.
To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
Adjust the heat air trigger temperature.
To lower the trigger temperature by 11
degrees F (6 degrees C), use setting
01. To lower the trigger temperature
by 7 degrees F (4 degrees C),
use setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency function
such as for power failure etc. Do not
start and stop the indoor unit by this
function in normal operation.
Be sure to operate by the control unit,
converter or external input device.
Restrain the cold airfl ow with making
the airfl ow lower when starting heating
operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.