AirStage ABYA54GATH Manuel d'installation - Page 8
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} AirStage ABYA54GATH. AirStage ABYA54GATH 17 pages. Indoor unit (ceiling type)
(1) Install insulation for the drain pipe.
Assemble as described below.
Assemble Drain hose (Accessories) and Hose band
(Accessories) to Drain port.
Soft PVC side
10 to 15 mm
Drain hose
(Accessories)
Wrap the drain hose insulation around the drain hose connection.
Drain hose insulation
(Accessories)
Hose opening view
Wind the attached heat insulation around the
hose band. Make sure the alignment is on top.
En-7
Drain port
Hose band
Drain hose
(Accessories)
(Accessories)
Drain pan
Ensure there is no space
Hose Band
(Accessories)
Soft PVC side
100mm
(2) If " 1 Right rear piping": fasten the drain hose with VT wire so that the pipe slopes cor-
rectly within the indoor unit.
Indoor unit (Rear view)
(3) Connect the drain pipe.
Hard PVC side
6. ELECTRICAL WIRING
]
Electrical work must be performed in accordance with this Manual by a person certifi ed
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insuffi cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fi re.
Before starting work, check that power is not being supplied to the all units.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the
allowable current can cause electric shock or fi re.
For wiring, use the prescribed type of cables, connect them securely, making sure
that there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheating the terminals, electric shock, or fi re.
Do not modify the power cables, use extension cables, or use any branches in the
wiring. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fi re.
Match the terminal board numbers and connection cable colors with those of the
outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fi re.
Always fasten the outside covering of the connection cable with the cable clamp. (If
the insulator is chafed, electric discharge may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical
box cover can cause serious accidents such as electric shock or fi re through exposure
to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
VT wire (Accessories)
Drain hose
Applying
area of
Joint pipe
adhesive
(Field supply)
Drain pipe (VP25)
(Field supply)
4 mm or less
WARNING