AirStage ARXB14GALH Manuel d'installation - Page 9
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} AirStage ARXB14GALH. AirStage ARXB14GALH 19 pages. Indoor unit (duct type)
4.4. Installing heat insulation
Install the heat insulation material after performing a refrigerant leak check (see the In-
stallation Manual for the outdoor unit for details).
4.4.1. COUPLER HEAT INSULATION
• Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid
pipe of indoor side.
• After installing the coupler heat insulation, wrap both end with vinyl tape so that there
is no gap.
• After affi xing the coupler heat insulation, secure it with 2 cable ties (large), one on each
end of the insulation.
• Make sure that the cable ties overlap the heat insulation pipe.
Coupler heat
insulation (Acces-
sories)
Cable tie (Large)
(Accessories)
After checking for gas leaks (refer to the Installation Manual of the outdoor unit),
perform this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
4.4.2. INSULATION (OUTLET)
When not using the air outlet duct, install the insulation (outlet) on the air outlet fl ange. (Fig. A)
1 Install the small pieces of insulation (outer/small) on the left and right sides of the air
outlet fl ange.
2 Install the large pieces of insulation (outer/large) on the upper and lower sections of
the air outlet fl ange.
Insulation (Outlet)
(Small)
(Accessories)
1
2
1
2
Insulation (Outlet)
(Large)
(Accessories)
Failure to install the insulation may cause water leaks.
Cover this portion with
heat insulation.
Heat insulation
CAUTION
Fig. A
View B
View A
0 mm
0 mm
CAUTION
5. INSTALLING DRAIN PIPES
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose (Table A).
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
Drain pipe
• CEILING CONCEALED TYPE
Drain hose
Outlet air fl ow
Good
Prohibited
Arrange the drain hose
lower than this port.
Good
1.5 to 2 m
• FLOOR STANDING CONCEALED TYPE
Good
Prohibited
• Installation method of Drain hose
• Be sure to connect the pipes for drainage without leakage.
• To avoid condensation and dripping, always insulate the indoor drain pipe.
(1) Be sure to use supplied Drain hose 1 and Hose band 2 (When using the Drain hole
on the other side of the unit, installation work is the same.)
2 Hose band (Accessories)
Drain
hole
Table A
O.D.
32 mm(VP25)
Trap
Prohibited
Rise
Supporter
Air bleeding
Prohibited
Rise
Prohibited
CAUTION
1 Drain hose (Accessories)
Hard PVC side
En-8