AirStage ARXC90GATH Manuel d'installation - Page 15
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} AirStage ARXC90GATH. AirStage ARXC90GATH 16 pages. Indoor unit (duct type)
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
ON
OFF
SW
SW
SW
1
2
3
Table B
A (Factory setting)
DIP switch SET3 SW1
DIP switch SET3 SW2
7.3. Switching the upper limit of cooling temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
ON
OFF
SW SW SW SW
1
2
DIP switch SET 4 SW3
OFF (Factory setting)
ON
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
1
Code change
A
B
C
D
A
B
C
Dip switch "SET 3"
SW
4
Custom code
B
C
OFF
ON
OFF
OFF
OFF
ON
DIP switch "SET4"
3
4
Table C
Cooling temperature setting range
Standard (18 to 30 °C)
Extension (18 to 32 °C)
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
D
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Filter indica-
11
tor interval
Filter indica-
13
tor action
Cool air
temperature
30
trigger
Heat air
D
temperature
31
trigger
ON
ON
Auto restart
40
Cool Air
43
Prevention
External
46
control
Error report
47
target
Fan set-
ting when
cooling
49
thermostat
OFF
Setting number
Default
○
00
Default
Adjust the fi lter cleaning interval notifi ca-
tion. If the notifi cation is too early, change
01
Longer
to setting 01. If the notifi cation is too late,
change to setting 02.
02
Shorter
○
00
Enable
Enable or disable the fi lter indicator.
01
Disable
Setting 02 is for use with a central remote
Display only on
controller.
02
central remote
controller
○
00
Default
Adjust the cool air trigger temperature. To
lower the trigger temperature, use setting
01
Adjust (1)
01. To raise the trigger temperature, use
setting 02.
02
Adjust (2)
○
00
Default
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
01
Adjust (1)
degrees C, use setting 01. To lower the
trigger temperature by 4 degrees C, use
02
Adjust (2)
setting 02. To raise the trigger tempera-
ture, use setting 03.
03
Adjust (3)
00
Enable
Enable or disable automatic system
○
restart after a power outage.
01
Disable
○
00
Super low
Restrain the cold airfl ow with making
the airfl ow lower when starting
Follow the
heating operation. To correspond to
setting on
01
the ventilation, set to 01.
the remote
controller
○
Allow an external controller to start
00
Start/Stop
or stop the system, or to perform an
emergency stop.
Emergency
01
* If an emergency stop is performed from
stop
an external controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor unit stops by
02
Forced stop
the input to the external input terminals,
and Start/Stop by a remote controller is
restricted.
○
00
All
Change the target for reporting errors. Er-
Display only on
rors can either be reported in all locations,
01
central remote
or only on the wired remote.
controller
Follow the
When set to 01, the fan stops when
○
setting on
the thermostat is OFF in cooling
00
the remote
operation. Connection of the wired re-
controller
mote controller (2-wire type or 3-wire
type) and switching its thermistor are
01
Stop
necessary.
Details
En-14