Figure 2
2.3 PLUMBING FIXTURE
Heaters are connected to plumbing fixtures as shown in (Figure 4, Figure 6).
For potential disconnection of the heater, the service water inlets and outlets must be
provided with screw coupling Js 3/4". The safety valve is mounted on the cold water inlet
identified with a blue ring.
Each hot service water pressure heater must have a safety valve with a membrane spring.
The safety valve must be easily accessible, as close to the heater as possible. The inlet pipes
must have at least the same clearance as the safety valve. Safety valve is placed high enough
to secure dripping water drain by gravity. We recommend mounting the safety valve onto
a branch pipe. This allows easier exchange without having to drain the water from the
heater. Safety valves with fixed pressure settings from the manufacturer are used for the
assembly. Starting pressure of a safety valve must be identical to the maximum allowed
heater pressure, and at least 20 % higher than the maximum pressure in the water main. If
the water main pressure exceeds such value, a reduction valve must be added to the system.
No stop valves can be put between the heater and the safety valve. During assembly, follow
the guide provided by the safety equipment manufacturer.