1.3 Technical datasheet

1.3.1 Push flow situation

Considering the normal process flow direction, the situation where the fan is located upstream of
the explosion source (Figure: 7).

1.3.2 Pull flow situation

Considering the normal process flow direction, the situation where the fan is located downstream
of the explosion source (Figure: 8).

1.3.3 Special conditions for safe use

Installation:
Installation, operation, maintenance and repair in areas with danger of explosions may only
be carried out by qualified personnel;
Ensure that no tools, nuts and bolts or assembly parts remain in the machine during assembly
or maintenance;
Selection and installation of the electrical parts within hazardous areas shall be fulfilled
according the EN60079‐14 and the installation instructions of the specific equipment;
No potential difference between all metal parts within the non‐return valve, or between
non ‐ return valve and earth may exist. Therefor earthing resistance between all metal parts
and earth shall be measured before operation and shall be maximum 1 MΩ between
Figure: 7 Push flow situation
Figure: 8 Pull flow situation