Anden A200V1 Manuel d'installation et d'utilisation - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} Anden A200V1. Anden A200V1 12 pages.
SET UP DEHUMIDIFIER FOR INSTALLATION
LOCATION CONSIDERATIONS
The dehumidifiers should be spaced evenly
throughout the area to be dehumidified with
the following recommendations:
1. Avoid placement where the discharge of
one dehumidifier is pointing toward the
inlet of another See FIGURE 1.
2. Account for handling dehumidifier
condensate by considering drain or sump
pump locations. See FIGURE 2.
3. Leave appropriate room on the electrical
service side to remove panel for field
connections. See FIGURE 3.
The recommended orientation is to install
the dehumidifiers around the perimeter
of the room with the dehumidifier inlet
pointing toward the wall and the outlet
pointed to distribute the dry air over the
canopy. This installation maximizes allowable
plant space and works with the existing
room fans to distribute air over the canopy.
FIGURE 2 – CONDENSATE DRAIN LOCATION
DRAIN FITTING
FIGURE 1 – PLACEMENT WITHIN SPACE
16"
MINIMUM CLEARANCE
FROM WALL TO
DEHUMIDIFIER
INLET
FIGURE 3 – SERVICE SIDE
90-2328
CANOPY
HEIGHT
FIELD WIRING
ACCESS
ELECTRICAL
SERVICE PANEL
90-2329
90-2328
3