Anderson Thermal Solutions – ANX70 Burner Operation Manual
safely installed before ignition. The ignition of the burner needs to be performed after the
combustion chamber is purged. If it is ignited at a low temperature, it needs to be replaced
with 5 times the volume of the combustion chamber to avoid explosion.
However, it is not necessary to purge when the temperature is higher than 750℃. Air pipe
or gas pipe connected with burner should be tight enough with no leakage, also the
periodically check air or fuel nozzles of the burners to prevent to be blocked by dust, slag
or other materials.
ATTENTION: DANGER OF BEEN BURNT
When burner in operation, combustion is severe, so the burner must be fixed. Hoses or
cables in area of the combustion system must be suitable for high temperature, to prevent
high temperature failure or cause safety accidents. Burners should be periodically
inspected and cleaned. Copper wire brush may be used, if necessary, to clean burner head.
The burner system should be checked twice a year for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output
position. Following interlocks will cause emergency stop, including gas low pressure, high
pressure or low combustion air pressure, as well as emergency stop is trigged, the main
power is out, UV signal failure or kiln safety conditions (such as high temperature limit, flue
system opening, etc.) will cause the burner lockout. Users need to know the maintenance
interval recommended by the manufacturer and the interval specified by national laws,
whichever is shorter.
4. Fuel Information
The following table shows the combustion fuel characters of natural gas, safety rules must
be obeyed when the operation carried out.
Fuel
Natural gas
Low Calorific value
35,900 [kJ/m
3
]
Composition
>98% CH
4
Reference conditions
1,013.25 mbar, 0°C
5. ANX70 Series Burner Description
ANX70 series burner is Anderson Thermal Solutions (Suzhou) Co., Ltd. patented nozzle
mixing burner, with staged combustion, utilize Flue Gas Recirculation and other designs to
Anderson Thermal Soluions(Suzhou)Co. Ltd.
2