9. Burner Installation

9.1 Storage:

1. Make sure that the area is clean.
2. Store the components in a cool, clean, dry room.
3. Keep the components in the original package as long as possible

9.2 Handing

1. Make sure that the components are clean and free of damage.
2. Protect the components from weather, damage, dirt and moisture.
3. Protect the components from excessive temperatures and humidity.
4. Use appropriate support equipment, i.e. harnesses, straps, chains, etc. when lifting
burner components.

9.3 Operation requirement

To make sure burner can be operated, the following issues should be checked.
1. Power voltage, frequency and stability.
2. Fuel type and pressure.

9.4 Burner Mounting

1. Mounting method
The installation modes of VFC86 burners are in the duct, the burner surface is vertical
to process air, downstream space should be long enough to avoid flame conflict with
the duct wall. Provide an opening in the duct 80mm gap on 4 sides of the burne.
2. Profile Plate Adjust
Profile plates are not required for good burner operation, but uniform velocity must
be maintained for the full length of the burner. If velocity is not uniform, profile plates
can be used to correct this condition. Profile plates should be positioned flush with
the firing end of the burner. If necessary, the plates can be located up to 1/2" back
from the firing end, but under no circumstances should they be in front of the burner.
3. Valve train connection
Locate the valve train as close as possible to the burner to make sure gas reach the
burner during the trial for ignition time. Sufficiently size shut off valves in the valve
train. In order to decrease pressure lost in pipe, minimize piping elbows to be used
while pipe union is recommended. Flexible hose is good optional but pressure loss
must be considered.
4. Flame monitoring
This type of burner is suitable for UV scanner as flame sensors, UV scanner can be
installed on pilot burner, or seperate UV scanner on burner side plate.

9.5 Checklist after installation

To verify the system was properly installed, perform the following checks:
– Be sure there are no leaks in the gas lines.
– Be sure all the components contained in the flame monitoring and control system,
pressure switch and wiring are properly installed.