ATIM Cloud Wireless DINDA Manuel de l'utilisateur - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} ATIM Cloud Wireless DINDA. ATIM Cloud Wireless DINDA 19 pages. Analog sensor reading

Set up

a. Positioning
Install the modem at a minimum height of 2m and not glued to a wall, ideally offset by at least 20cm.
For best results, it is advisable to move the antenna up and clear of any metal obstacle within a radius of
1 meter if possible.
b. Modem connection
Terminals:
Antenna (SMA):
directly to the SMA connector or via a 50Ω cable in case of antenna offset
Alimentation device (Lower terminal):
30V that can provide a minimum current of 100mA.
Alimentation analogical sensor (Lower terminal):
that of the external power supply (or terminal GND). This output can deliver a max current of 1
ampere with the supply voltage (10 / 30V). Before each analog measurement, the sensor will be
powered for 0.5 seconds. If you want to permanently supply the sensor, do not use the "OUT"
connector and connect it directly to the terminals of the external power supply.
Name
GND
10/30V
Alimentation between 10V and 30V
OUT
AN
IN2
IN1
Before powering the product, a 50Ω / 868MHz antenna must be connected, either
The ACW-GW module must be powered with a DC power supply between 10V and
The analog sensor can be powered at the time of measurement directly with the output
OUT of the ACW_DA. To do this connect its power supply to the pin "OUT" and its GND to
ATIM_ACW-DINDA_UG_FR_v1.5
Designation
Ground
Alimentation sensor
Analogic input
Numerical input 2
Numerical input 1
Input / Output
Input (alimentation)
Ground
Output TOR 10/30V (1A)
Input 0/10V | 4/20mA
Input TOR 10/30V
Input TOR 10/30V
.