Supplement operating manual for DREHMO i-Matic actuators with integrated

2.5 Electrical connection

2.5.1 Actuators i-Matic for normal operation – DiM-X0X
2.5.1.1

Compact plug assembly

The electrical connection is done on the wiring board DiM-19 which is assembled on a
mounting plate in the compact plug housing. As an example for explanation, the cable
assembly for i-Matic with redundant field bus and optional two analogue and four digital
process inputs as inner parts of the compact plug is given below.
Strain relieves incoming, outgoing bus and
optional process inputs are independently
switchable to ground (switches on the front
side)
(1)
Optional: external 24 VDC supply of i-Matic unit (input) with tolerance +10%, -5%
and less than 500mA load.
Optional: auxiliary 24 VDC supply (output) for external use allows 60mA load.
Wenden, 21.03.12
Prepared by: Ste
MODBUS fieldbus interface
Mounting plate for power connector
and wiring board (backside view)
Power connector wire size 0.5 to 2.5
mm². Standard: cage clamp
Optional: screwing terminals
Various screwing terminals
depending on ordered options:
terminal size: AWG 16..26
solid wire: 0.14 to 1.5 mm²
flexible wire: 0.14 to 1 mm²
Two optional analogue inputs
Four optional digital inputs
Channel 2 incoming and outgoing
RTS signals
Optional 24V external power
Channel 1 incoming and outgoing
Page 12 of 18