Atkinson Electronics GSCM-MINI-50 Manuel - Page 10
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Atkinson Electronics GSCM-MINI-50. Atkinson Electronics GSCM-MINI-50 12 pages. Generator start control module - mini (2 wire to 3 wire)
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
GSCM-MINI-50HZ
APPLICATION 3 - OUTBACK 2 WIRE START TO 3 or 4 WIRE GENERATOR START CONTROL
The GSCM-mini can be used with Outback invertors and most 3 wire gas generators . The 2 wire invertor generator start
output is a switched 12VDC signal, the GSCM-mini was designed to accepts the switched 12VDC start signals from the
Outback Inverter and provides two relay contact outputs that can be wired as three or four wire Start/ Stop configurations
(see page three for generator wiring configurations). The GSCM-mini monitors the generators AC output to know when
to dis-engage the starter, if an Over/Under Hz condition has accrued (Optional), and when the generator has shutdown,
either by command or by fault. An optional manual On-Off-Auto switch can be used to manually turn on or off the
generator, or run automatically from the inverter (see above drawing). When a start signal is received the the GSCM-
mini starts the generator. After the generator starts and comes up to speed the "run" LED lights on the mini. If the
generator fails to start or fails while commanded to run the "fault" LED on the GSCM mini lights. Turning off the power
to the GSCM mini either by emergency shutdown switch or an optional power On/Off switch, for 5 seconds and then back
on, resets the fault condition and the mini is ready to receive another start command.
ATKINSON ELECTRONICS, INC.
REV 5/08
Web Site: www.atkinsonelectronics.com
Distributed by: