Advanced settings:

Display text 
Configuration 
Option 
A‐Y 
RH Ambient 
Response  
P‐Y 
RH Rapid 
Response 
enable 
Settings
Speed selection
Set trickle and boost speeds in l/s by using the
To convert m3/h to l/s, divide the m3/h by 3.6 (e.g. 54m3/h / 3.6 = 15 l/s).
The Trickle Speed cannot be higher than the Boost selection. Therefore it might be
necessary to modify the Boost selection before increasing the Trickle setting.
If "0" is selected for the trickle speed, the fan will be off until a boost signal is activated
(for example via LS/ pullcord/humidity).
Boost time
The boost setting allows the boost timer to be adjusted from 1-30 minutes, the default
is 15 minutes. This option may also be disabled, thus removing the option from the
menu and setting the overrun to 0.
Inbuilt Ambient Response Humidistat with Rapid Rise Detection
The humidity threshold setting defines at what relative humidity the fan will trigger,
adjustable from 40% to 90% rH. The fan increases in speed slowly between the trickle
and boost speeds between the trigger %rH and +10%. The trigger point will
automatically adjust if the temperature drops below 18C to prevent nuisance triggering.
The fan also incorporates a rapid rise function to detect rapid rises in humidity when the
ambient %rH is under the threshold setting. If a rapid rise is detected the fan will
increase in speed proportionally between the trickle and boost settings until the
humidity lowers again.
Comfort mode
 With comfort mode disabled, the fan will go into boost as soon as an LS (Light
Switch) input is detected and over-run for the set period after LS is disconnected.
 With comfort mode enabled, the fan will remain off / in trickle up to a maximum of
20 minutes. Once LS is deactivated, fan will run at boost mode for the length of
time LS was present up to a maximum of 20 minutes plus the set over-run time.
If the LS was activated for < 3 minutes, no boost will occur to prevent nuisance
activations.
Selections 
A‐Y Ambient Response 
enabled 
p‐Y = Rapid Response enabled 
A‐n Ambient Response disabled 
p‐n = Rapid Response disabled 
and
buttons.
Default 
Enabled