Atlantic Boilers COMPACTE Manuel technique - Page 9

Parcourez en ligne ou téléchargez le pdf Manuel technique pour {nom_de_la_catégorie} Atlantic Boilers COMPACTE. Atlantic Boilers COMPACTE 14 pages. Electric boilers

Atlantic Boilers COMPACTE Manuel technique
• Check that the system is filled with water
• Purge the system
• An automatic air vent is required on the flow from the boiler
• Power the boiler
• Switch the boiler on
• Set the two regulation stages
If the boiler is powered without any water, it will cause the immersion heaters or
sensors to fail (no warranty)
Controls
Factory settings (stage 1: 80ºC, stage 2: 75ºC)
Adjustment
Nota:
+ Set 1 = Stage 1
+ Set 1 must always be > Set 2
+ Minimum setting temperature +20ºC
+ Maximum settings temperature +90ºC
+ Starting point stage 1: 3ºC under the setting temperature, with 3
minutes confirmation time
+ Starting point stage 2: 2ºC under the setting temperature, with 3
minutes confirmation time
+ Each stage to be stopped when the settings temperature has been
reached

STARTING THE BOILER

1. Display
2. Stage selector (adjustment & control)
3. Settings +
4. Settings –
5. Operation light
6. Control stage light on
7. Alarm light
Set 2 = Stage 2
9