3 - INSTALLATION
Always read this guide carefully before
working on the
unit and keep it in a safe place for future
reference.

3.1 - Choice of location

The intended location of the unit should be
fully accessible so as
to ease servicing and maintenance
operations and allow easy
removal of the plates from the side of the
unit (Fig. 3). Adequate
clearance must be left in front of the safety
and control devices.
A
A
Fig. 3
Fig. 3
3.2 - Installation

3.2 - Installation recommendations

3.2 - Installation recommendations
recommendations
• CIPRIANI plate heat exchangers have a limited operating
• CIPRIANI plate heat exchangers have a limited operating
• Atlantic plate heat exchangers have a
pressure and temperature range. Install all the necessary
pressure and temperature range. Install all the necessary
safety devices to prevent overrunning the limits specified
safety devices to prevent overrunning the limits specified
limited operating
on the order documents. Approval to use the plate heat
on the order documents. Approval to use the plate heat
pressure and temperature range. Install
exchangers at higher conditions must be obtained from CIP-
exchangers at higher conditions must be obtained from CIP-
all the necessary safety devices to prevent
RIANI. It is recommended to fit pressure and temperature
RIANI. It is recommended to fit pressure and temperature
test points near the unit.
test points near the unit.
overrunning the limits specified on the
• Make sure that the heat exchanger is compliant with the
• Make sure that the heat exchanger is compliant with the
order documents. Approval to use the
safety rules in force on the site of use (explosive atmos-
safety rules in force on the site of use (explosive atmos-
phere, etc.).
phere, etc.).
plate heat exchangers at higher conditions
• Affix appropriate visual warning sign wherever the surface
• Affix appropriate visual warning sign wherever the surface
must be obtained from Atlantic .
temperature above 60°C or below 0°C.
temperature above 60°C or below 0°C.
• If the heat exchanger is to be installed on framework, the
• If the heat exchanger is to be installed on framework, the
It is recommended to fit pressure and
temperature test points near the unit.
• Make sure that the heat exchanger is
compliant with the
safety rules in force on the site of use
(explosive atmosphere, etc.).
• Affix appropriate visual warning sign
wherever the surface
temperature above 60°C or below 0°C.
• If the heat exchanger is to be installed
on framework, the 35 structure must be
designed to withstand the weight of the
minimum recommended
minimum recommended
value (mm)
value (mm)
Model
Model
A
DN32
DN32
700
700
DN50
DN50
1000
1000
DN65
DN65
1000
1000
DN100
DN100
1500
1500
DN150
DN150
1500
1500
DN200
DN200
2000
2000
exchanger when in operation (filled) and
with its accessories.
• If necessary, affix the hazard symbol
corresponding to the fluid in accordance
with applicable standards.
• Take all appropriate steps to mitigate
the effects of any significant human,
environmental or financial consequences
of failure.
• Make sure that the heat exchanger is
always installed vertically, stable, and
secured using all its anchorage points. If
necessary, fit additional anchors suitable
for the foreseeable stresses.
• Install drains and vents, shut-off valves,
A
and fill and drain valves on the pipes so
that the heat exchanger can be serviced
without disrupting the system.
• In the event of seasonal use, drain the
heat exchanger completely to prevent any
risk of freezing or corrosion if a corrosive
fluid is used.
• If accessories are installed on the
heat exchanger, refer to their specific
instructions.

3.3 - Hydraulic connections

• To keep the insides of the pipes clean,
do not remove the seals on their ends until
you are ready to make the hydraulic
connections.
• The insides of the pipes must be free
of all foreign matter (sand, welding slag,
other solid matter, etc.) that could damage
the plates and gaskets.
• Filtration: If the fluids to be circulated
through the heat exchanger contain
suspended matter, a filtration system of up
to 500 μm must be installed.
• Check the tightening dimension
specified on the nameplate. Refer to
section 5.7 if retightening is needed.