Atlantic Boilers RS TURBOFLOW DN 200 S990+ Manuel d'utilisation et d'entretien - Page 14
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation et d'entretien pour {nom_de_la_catégorie} Atlantic Boilers RS TURBOFLOW DN 200 S990+. Atlantic Boilers RS TURBOFLOW DN 200 S990+ 18 pages. Plate heat exchangers
If you feel it is necessary to tighten beyond the recommen-
ded dimension,contact CIPRIANI's After-Sales Department
fluid
to obtain advice.
dards
h the
gainst
hat all
Fig.10
a ho-
• It is recommended to perform a pressure test after all main-
5.8 - Reassembly
cified
tenance on the plates and gaskets in order to check the
heat exchanger's internal and external tightness. The maxi-
• Before reassembling the heat exchanger,
mum pressure for each circuit should be equal to the ope-
make sure that all the plates and gaskets are
rating pressure and should never exceed the rated pressure
n the
(PS) specified on the nameplate. The recommended testing
clean and free of grease.
e.
time is at least 10 minutes. Nevertheless, it remains the
e fra-
user's responsibility to check national standards and local
• When arranged correctly, the stacked plates
order
codes affecting such a test. If different test conditions are
ained
required, please note that the heat exchangers should ne-
form a honeycomb pattern (Fig.10).
ed on
ver be tested at pressures greater than the test pressure
(PT) specified on the nameplate and that the pressure diffe-
• The order of assembly and the plate
direction are specified on the plate
arrangement drawing
.
Procedure
• Starting from the frame plate, assemble the
plates on the bar one by one with the gaskets
facing the frame plate.
• Clean and lubricate the tie-rods, position
them on the frame, then tighten the nuts
gradually and evenly in the order indicated in
Fig. 11 until the correct dimension is obtained
between the plates (tightening dimension),
as specified on the nameplate. Check that
rences between the two circuits during testing should never
this dimension is the same on each side.
be higher than the maximum allowable differential pressure.
Overtightening may irreversibly distort the
• If a leak occurs, lower the pressure then retighten the nuts
and repeat the test. If the leak persists, check the gaskets
plates. If you feel it is necessary to tighten
and plates for signs of wear, damage or dirt. If necessary,
beyond the recommended dimension,contact
replace the gaskets.
Atlantic to obtain advice.
• It is recommended to perform a pressure
5.9 - Plate types
test after all maintenance on the plates and
gaskets in order to check the heat exchanger's
internal and external tightness. The maximum
pressure for each circuit should be equal to the
operating pressure and should never exceed
the rated pressure
(PS) specified on the nameplate. The
recommended testing time is at least 10
minutes. Nevertheless, it remains the user's
responsibility to check national standards and
local codes affecting such a test. If different test
conditions are
required, please note that the heat exchangers
ATLANTIC BOILERS, PO BOX 11, ASHTON UNDER LYNE, OL6 7TR T: 0161 621 5960 E: [email protected] www.atlanticboilers.com
The letter indicates the plate type:
Fig.11
A
B
should never be tested at pressures greater than
the test pressure (PT) specified on the nameplate
and that the pressure diffeences between the two
circuits during testing should never
be higher than the maximum allowable
differential pressure.
rences between the two circuits during testing should never
• If a leak occurs, lower the pressure then
be higher than the maximum allowable differential pressure.
retighten the nuts and repeat the test. If the leak
• If a leak occurs, lower the pressure then retighten the nuts
persists, check the gaskets and plates for signs of
and repeat the test. If the leak persists, check the gaskets
wear, damage or dirt. If necessary, replace the
and plates for signs of wear, damage or dirt. If necessary,
gaskets.
replace the gaskets.
5.9 - Plate types
The letter indicates the plate type:
A = HIGH EFFICIENCY plate with wide chevron pattern
B = LOW DELTA P plate with narrow chevron pattern
PORT HOLES FOR PLATES ON SINGLE-PASS UNITS
ODD
EVEN
DESCRIPTION
INITIAL
INTERMEDIATE
PARALLEL
FLOW
CODE
1 2 3 4
1 2 3 4
PORT HOLES POSITION FOR DEVIATION PLATE
PORT HOLES POSITION FOR DEVIATION PLATE
1,2,4
1,3,4
1,2,3
2,3,4
Drilling the collectors. Code which indicates the position and the open or
closed status of the collectors.
1234 = Open 0 = Closed
e.g.: 1204: indicates that porthole No. 3 is closed.
A
B
ODD
ODD
INTERMEDIATE
FINAL
1 2 3 4
0
1,4
2,3
3
3
PORT HOLES
POSITION
PASSING
HOLES
BLIND
HOLES