Atlantic Ultraviolet MIN-3 Manuel du propriétaire - Page 5
Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Atlantic Ultraviolet MIN-3. Atlantic Ultraviolet MIN-3 16 pages. Ultraviolet water purifiers
Également pour Atlantic Ultraviolet MIN-3 : Manuel du propriétaire (16 pages)
INSTALLATION
L
OCATION
1. The water purifier is intended for indoor use only. The water purifier is designed to mount horizontally. The water purifier
should be protected from the elements and from temperatures below freezing. The ambient temperature, in the area
surrounding the water purifier, should be between 35
2. Electrical power supplied to the water purifier MUST match power requirements listed on the water purifier. Use of a voltage
surge protector is recommended.
3.
CAUTION: Install water purifier within 48" of a known good ground. Water Purifier will need to be installed
into approved ground fault circuit interrupt (GFCI) receptacle. Where a 2-prong or unprotected 3-prong receptacle is
encountered, it must be replaced by a properly grounded Ground Fault Circuit Interrupt (GFCI) receptacle. Installation must
be in accordance with the National Electrical Code and any local codes and ordinances by a qualified electrician.
4. The water purifier should be located in a dry, well-lit area, which provides enough room to perform routine maintenance.
This includes a minimum distance of one chamber length from the chamber end, to allow for cleaning and/or the
changing of the lamp and quartz sleeve as well as a minimum of 6" on the opposite end of the water purifier. Minimum
clearance to floor 18''.
5. The water purifier should always be located closest to the point of use. This reduces the chance of the purified water being
re-contaminated by bacteria in the water distribution system after the water purifier.
6.
CAUTION: As with any water handling device, the water purifier should be located in an area where any possible
condensation or leakage from the water purifier, any purifier accessory and/or plumbing will not result in damage to the
area surrounding the water purifier. For added protection, it is recommended that a suitable drain pan be installed under the
purifier. The drain pan must be plumbed to an adequate, free flowing drain to prevent water damage in event of a leak. There
are numerous leak detection/flood stop devices, available on the market today, designed to stop flow of water, reducing the
chance of water damage due to leakage. For more details regarding leak prevention and/or limiting damages due to leaks
please contact factory.
7. The water purifier should be located after all other water devices, such as De-ionizers, Water Softeners, Carbon Filters, Pre-
Filters, Reverse Osmosis, Pressure Tanks, and Pumps. This reduces the chance of the purified water being re-contaminated by
bacteria in any of these units.
R
I
ECOMMENDED
NSTALLATION
COMMON
PRE-TREATMENT or
PUMPING DEVICES
Incoming
1. Deionizer
Water
2. Water Softener
Supply
3. Carbon Filters (GAC)
4. Pressure Tank
5. Pump
6. Reverse Osmosis
7. Prefilters
Ultraviolet Water Purifiers
should be installed closest
to the point of use. (POU)
Note: Drain Pan
Recommended. Water
purifi er should be installed at
minimum of 18" above fl oor
120v 50/60Hz using ballast no. 10-0508B has
a ground wire attached.
230v 50/60Hz using ballast no. 10-0504B has
a ground wire attached.
o
Figure 1 - Recommended Installation
Cold Water Line
OPTIONAL EQUIPMENT
Flow Control Valve
5 Micron
Filter
Valve
Union
F and 100
F.
o
Elbow
Elbow
Ultraviolet
Water Purifier
OPTIONAL EQUIPMENT
Mounting Kit
POINT OF USE (POU)
Ultraviolet Water Purifiers
should be installed closest
to the point of use.
Outlet Line to point of use
to be as short as possible
Valve
Union
22"
Recommended Minimum
Clearance for Lamp or
Quartz Sleeve Removal
5