SYNCHRONIZING SYSTEM FUNCTIONS
Device
Number
Function
Sync Check
Phase Angle Window
Upper Voltage Limit
Lower Voltage Limit
25
Delta Voltage Limit
Delta Frequency Limit
Sync Check Time Delay
Dead Voltage Limit
Dead Time Delay
* Of nominal voltage.
Sync Check may be operated as a stand‑alone function or supervised by 79 (reconnect). Various combinations
of input supervised hot/dead closing schemes may be selected.
Phase Undervoltage
27
Pickup #1, #2
Time Delay #1, #2
* Of nominal voltage.
** When DFT is selected, the time delay accuracy is 2 cycles. When RMS magnitude is selected, an
additional time delay from 0 to +20 cycles may occur.
Directional Power
32
Pickup #1, #2
Time Delay #1, #2
The per‑unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings
for currents less than 14 A (2.8 A). This function can be selected as overpower or underpower in the forward
direction (positive setting) or reverse direction (negative setting). This function can also be selected for single
phase detection for line‑to‑ground VT.
Minimum sensitivity of 100 mA for 5 A CT (real component of current).
* Accuracy applies for a nominal current range of 2.5 A to 6 A (5 A CT) or 0.5 A to 1.5 A (1 A CT).
Negative Sequence Overvoltage
Pickup #1, #2
47
Time Delay #1, #2
* Of nominal voltage.
Inverse Time Overcurrent
Pickup
51
Characteristic Curve
Time Dial
Values in parentheses apply to 1 A CT secondary rating.
Setpoint
Ranges
0° to 90°
100.0 to 120.0%*
70.0 to 100.0%*
1.0 to 50.0%*
0.001 to 0.500 Hz
1 to 8160 Cycles
0.0 to 50.0%*
1 to 8160 Cycles
4 to 100%*
1 to 8160 Cycles
–3.00 to +3.00 PU
1 to 8160 Cycles
4 to 100%*
1 to 8160 Cycles
0.50 to 12.00 A
(0.10 to 2.40 A)
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
0.5 to 11.0
0.05 to 1.10 (IEC curves)
–3–
M‑5625 Digital Synchronizing System
Increment
Accuracy
0.1%
0.5 V or 0.5%
0.1%
0.5 V or 0.5%
0.1%
0.001 Hz
0.001 Hz or 5%
1 Cycle
0.1%
0.5 V or 0.5%
1 Cycle
2 Cycles
0.1%
0.5 V or 0.5%
1 Cycle
2 Cycles**
0.01 PU
0.02 PU or 2%*
1 Cycle
2 Cycles
0.1%
0.5 V or 0.5%
1 Cycle
2 Cycles
0.01 A
0.1 A or 3%
(0.02 A or 3%)
0.1
3 Cycles or 10%
0.01
1°
0.5 V