Networked Wireless Occupancy Sensor (WOS2-WM)
®
1
Installation Process (continued)
7. Exit Installation Test Mode. Momentarily press the Utility
button again, or wait 5 minutes for the mode to time out.
8. The sensor attempts to join a ZigBee network for up to 30
seconds. If it is able to join, the Network LED turns on solid for
10 seconds. If it is unable to join, it automatically retries every
15 minutes until it succeeds in joining a network. Note, the
sensor will not be able to join a network until a Wireless Area
Controller (WAC) is commissioned. See LED Operation and
Joining the ZigBee Network.
Daylight Hold-Off
LED Operation
Green LED:
Description
Network Indicator
Device is trying to join ZigBee network.
Rapid flash (12 times
If it fails to join, it will retry after 15
per second) for up to 30
minutes. See the Joining the ZigBee
seconds
Lighting Control Network section for
details.
Device successfully joined a ZigBee
Solid for 10 seconds
network.
Utility button was pressed to initiate
Flashes once
Installation Test Mode.
Utility button was pressed for 2
seconds and the device is currently
Flashes twice
joined to a network.
Batteries low. Replace the batteries.
On for 2 seconds every
Low battery warning in CSM-DP.
30 seconds
Red LED: Installation
Test Mode, Motion
Flashes at the rate of 2
times per second to 12
times per second
Off
PIR Sensitivity
* A network join can be retriggered manually at any time using one
On/off button
of the following methods:
Reset to factory defaults: This causes the device to leave any
network to which it is currently joined. Following the reset, the
device attempts to join a network. Press and hold the Utility
Mounting
button for 5 seconds. Release the button when the Network
Bracket
LED begins to flash rapidly.
Activate device: Press and hold the Utility button for 2 seconds.
If the device is already joined to a network, the Network LED
flashes twice. If the device is not joined to a network, the
Network LED flashes rapidly and the device will attempt to
join a network.
Battery
Compartment
For more information about configuring the lighting control
network, see the instructions and on-line help provided with the
DCS web application.
2
Joining the ZigBee Lighting Control Network
After successfully completing the Installation Test the occupancy
sensor is ready to communicate with the Daintree Wireless Area
Controller (WAC) and the Daintree DCS web-based lighting
management user interface. For more information about
configuring the lighting control network, see the instructions
and on-line help provided with the DCS application.
3
Placement
The PIR sensor can only be installed indoors. It is extremely
important to select the appropriate installation location to avoid
false occupancy reporting while obtaining the best sensitivity.
A proper installation should meet the following conditions:
• T he PIR sensor is typically mounted 6.5' to 10' (2m to 3m) from the
floor, with a 15 degree vertical tilt. The height, tilt, and angle of the
installation affects the coverage area.
• The PIR sensor must be 4' to 6' away from hot or cold sources so
on. The PIR sensor should not be installed in places with strong
air flows.
• The PIR sensor must have clear line of sight to the coverage area.
It may not detect a human body if it is blocked by furniture,
fixtures, large plants, glass, curtains, and so on.
• Install the detector securely to the ceiling or wall to minimize
sensor vibration. The PIR sensor should not be installed on doors or
windows, nor exposed to direct sunlight. The resulting hot air and/
or motion can cause false activation.
• The effectiveness of the PIR sensor is highly related to the direction
of human motion.
2
Installation Guide
Description
Installation Test Mode is active. The red
LED flashes at a speed proportional to
the amount of light detected. At the
minimum light level it flashes 2 times
per second. At the maximum light level
it flashes 12 times per second.
Normal operation. Installation Test
Mode automatically exits after 5
minutes.