Daintree DT108 Manuel d'installation - Page 3

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Daintree DT108. Daintree DT108 4 pages. Wireless occupancy sensor, ceiling mount

Daintree DT108 Manuel d'installation
Daintree
Networked Wireless Occupancy Sensor, Ceiling Mount (WOS2-CM)
®
3
Placement (continued)
• The PIR sensor must have clear line of sight to the coverage area.
It may not detect a human body if it is blocked by furniture,
fixtures, large plants, glass, curtains, etc.
• Install the detector securely to the ceiling to minimize sensor
vibration. The PIR sensor should not be installed on moveable
objects, nor exposed to direct sunlight. The resulting hot air and/
or motion can cause false activation.
Coverage Pattern, WOS2-CM-E, Extended Coverage
Installation Height
10' (3m) from floor
Detection Angle
120°
Detection Radius
up to 17' (5.2m)
4
Adjustments
Two trimpots next to the
battery compartment are
used to adjust the Daylight
Hold-Off threshold
and PIR motion
sensor sensitivity
Use caution when
adjusting the trimpots.
Do not use excess force,
as this will
damage the unit.
Stop turning
the trimpot when
you feel resistance.
5
PIR Sensitivity
Turn the trimpot clockwise
to increase sensitivity.
Turn the trimpot counter-clockwise
to decrease sensitivity.
3
Installation Guide
Minimum
Maximum
(counter-
(clockwise)
clockwise)