OPERATING INSTRUCTIONS
The following instructions are intended to serve as a guideline for the use of the 3M
Monoxide Monitor. It is not to be considered all-inclusive, nor is it intended to replace the policy
and procedures for each facility.
•
Your employer must provide breathing air that meets at least the requirements of the
specification for Grade D breathing air, as described in the Compressed Gas Association
Commodity Specification G-7.1-1997 in the United States. In Canada refer to CSA
standard Z180.1, for the quality of the compressed breathing air. Failure to do so may
result in sickness or death.
•
Use of equipment described in these User Instructions must be in accordance with
applicable health and safety standards, or pursuant to the recommendations of an
industrial hygienist.
•
Each person using this equipment must read and understand the information in these
User Instructions before use. Use of this equipment by untrained or unqualified persons,
or use that is not in accordance with these User Instructions, may adversely affect product
performance and result in sickness or death.
If you have any doubts about the applicability of the equipment to your job situation, consult an
industrial hygienist or call 3M's Occupational Health and Environmental Safety Division Technical
Service Department 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.
Normal Operation
– The monitor will analyze the compressed air and show CO content on the display, in parts per
million (ppm).
– The green NORMAL light will glow continuously and the red ALARM light will flicker about
every second.
– When the CO concentration reaches the alarm point (10 ppm for USA, 5 ppm for Canada) the
red ALARM light will come on steady, the green NORMAL light will go off, the buzzer will
sound a steady tone, and the REM ALARM jack will be energized.
– When the CO concentration drops below the alarm setting, the indicators will automatically
return to normal.