Ansell 406143529 Instructions d'installation - Page 2

Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} Ansell 406143529. Ansell 406143529 2 pages. Falcon 6500k led surface emergency downlight - self test – ip65

®
Self Test
Operating and recommended Routine Test Procedure
Please refer to the literature below as to the functionality of Self Test Emergency.
Read these instructions carefully to ensure safe and reliable operation of this emergency luminaire. The following operations are
designed to ensure the continued protection of your premises and occupants, in the event of the possibility of a failure of the normal
lighting supply.
The self test unit inside this product is designed to test the fitting in accordance with current legislation BS EN 62034:2012.
When the unit is first installed the fitting will randomly select a test date of between 200 and 365 Days.
Once this date is set it will continue to test at the same time every year for a full 3 hour test.
Once the product has been on charge for 24hrs, the luminaire will discharge for 5 seconds for test purposes.
Every 30 days the installation will be tested for 10 minutes.
The luminaire will show a constant Green LED in normal condition.
Using the "reset" button you can press for 1 second and you can reset the random testing or press for 3 seconds to simulate a 5
minute emergency test.
During the emergency testing the luminaire will test the following:
The battery connection
Emergency operation time
Lamp / LED operation
Should a fault occur then the following can be observed:
If there is a failure of the battery such that it becomes disconnected then there will be a continuous red LED.
If the system fails the 10minute / 3 hour duration test then the red LED will flash slowly
If the lamp / LED's fail the red LED will flash quickly.
If there is a fault indicated as per any of the above and the luminaire is repairable, the indicated fault will not cease until the repair
has been completed and the supply is reinitiated.
Should there be a supply failure to the luminaire the emergency mode will activate. When the supply is reinitiated, the luminaire will
continue with the same testing period as before. The self test date will be stored within the luminaire for 7 Days.
Warning
Disconnect the mains supply and unplug the battery leads before working on the unit.
Failure to comply with these instructions may result in irreparable damage to the emergency control gear.
This product must not be modified in any way as this will negate any Safety approvals, and may render the product
inoperable or unsafe. The product must be installed in accordance with the instructions.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.This luminaire contains no serviceable parts.
2.The battery in this appliance can be replaced, but should only be undertaken by qualified personnel.
3.The emergency battery pack will need to be replaced after 3-4 years of use. Replace the battery with one of the same size and with the same
specification. (Battery Specification 3.6V 3000mAh Ni-Cd.)
4. If after the full three-hour duration test the appliance does not meet the rated duration then either the battery or whole fitting must be replaced.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information. RoHS - All components and materials used in this product are RoHS
2002/95/EC compliant.
Page 2.
Ansell Electrical Products, Unit 6B, Stonecross Ind. Park, Yew Tree way, Warrington, WA3 3JD
IP65
www.anselluk.com