Warning
Failure to comply with these instructions may result in irreparable damage to the emergency control gear.
This product must not be modified in any way as this will negate any Safety approvals, and may render the product inoperable or unsafe. The
product must be installed in accordance with the instructions.
Operating and recommended Routine Test Procedure
Follow these instructions carefully to ensure safe and reliable operation of this emergency luminaire. The following testing is designed to ensure the
continued protection of your premises and occupants, in the event of the possibility of a failure of the normal lighting supply.
Testing should be carried out in accordance with the recommendations of BS5266-8:2004 Clause 7.2.
A daily check – check LED charge indicator is illuminated
A monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker.
Ensure normal supply is restored after test and ensure charge indicator is illuminated.
One annual full three hour duration test - simulate a mains supply failure for a one hour continuous test by operation of key switch or
switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated.
To assist with this testing, a test record is included. If the luminaire fails any of the above tests, please contact a qualified electrician.
TEST RECORD SHEET
FIRST YEAR
TEST
MONTH
Signed
FUNCTIONAL
1
FUNCTIONAL
2
FUNCTIONAL
3
FUNCTIONAL
4
FUNCTIONAL
5
FUNCTIONAL
6
FUNCTIONAL
7
FUNCTIONAL
8
FUNCTIONAL
9
FUNCTIONAL
10
FUNCTIONAL
11
3 HOUR
12
-
Luminaire not suitable for covering with thermally insulating material.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Maintenance:
1. This luminaire LED contains no serviceable parts.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information. RoHS - All components and materials used in this product are RoHS
2002/95/EC compliant.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------