Bourns 1251-120S-N1 Instructions d'installation - Page 2
Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} Bourns 1251-120S-N1. Bourns 1251-120S-N1 2 pages. Hardwired ac hybrid h-spd
Installation
Figure 1
F1
N
L1
L2
L3
GND
Fusing installation not required but recommended for Type 1
SPD installation according to UL 1449. Mandatory for Type 2.
Introduce accessory
on SPD output for tightness
Wiring
Version N2
Green/Yellow wire
N
L1
L2
L3
Black wires
Maintenance
: ALL LED ON = system fully protected
07/16
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different
applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
Main switchboard
or sub-panel
Panel
wall
Nut
13 mm (0.5 in.) knockout (trade size)
Actual hole size 22 mm (.875 in.)
Black wires
White wire
GND
Green/Yellow wire
White wire
INSTALLATION INSTRUCTIONS
1. Disconnect breaker supplying all power to the equipment
prior to SPD installation.
2. See Figure 1.
3. Confirm Model 125x Series device is rated for your
system by comparing voltage measurements to the
Line Voltage on the product label.
4. Install in accordance with the applicable electric code in
your area.
5. Confirm that the electrical terminals used to attach this
device are identified for these conductors.
6. Twist conductors 1/2 turn or more for every 12 inches of
length.
7. Keep conductor length as short as possible with no sharp
bends.
8. Do not loop or coil wires.
9. Ensure a high quality ground is in place.
Diagnostic Operation
LED ON = Normal operation.
LED OFF (one or more) = Fault, check phase voltage and
connections. If okay, replace unit.
AUDIBLE ALARM ON = Fault, check phase voltage and
connections. If okay, replace unit.
Dimensions (inches)
Version N1
4
: ALL LED ON = system fully protected
0.79
0.83
: 1, 2 or 3 LED OFF = system unprotected
1251 & 1252 Series
Hardwired AC Hybrid H-SPD
3.46
0.81
0.78
2.44
and replace
with 125x-xxx-Nx