PLANNING
3.
Planning
Several things need to be considered when planning for the location of the SignalOn Series chassis. Some of these are:
• Chassis should only be installed in restricted access areas (dedicated equipment rooms, equipment closets, etc.) in
accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
• When using open relay-rack style network bays, spacing between bays and at lineup ends may be required depending
on the quantity and type of coaxial cable entering the bays. When spacing bays 0, 5, or 10 inches, verify that vertical
jumper rings will fit between bays.
• A fully loaded chassis may terminate up to two-hundred cables. Consideration should be given to the number of chassis
installed in a rack to prevent cable congestion.
• Allow sufficient room for cable management behind the chassis. Also leave sufficient vertical and horizontal cable
pathways above and below the chassis.
SignalOn
Series – RF Passive Modules - Installation & Operation Manual
®
ATX Confidential & Proprietary
CHAPTER 3: PLANNING
3-1