Configuration Menu

Item
HP
HVAC
Parameters
1
Temperature format
2*
Balance point low
3*
Balance point high
4*
Defrost point
5*
Installation type
6*
interstage delay
7
Low temperature limit
8
High temperature limit
9
Cycles per hour
10
Heat type
11
12
Smart Fan
13
Temperature setback
Outdoor temperature
14
Humidifier
15
operating mode
Automatic humidity
16
adjustment
Humidity setpoint
17**
Humidity offset
*
Parameters 2 to 6 are not available when the controller is configured for 1H1C, 2H2C or 3H3C heat pump.
**
Only parameter 17 is available when the controller is in user mode (SW1-2 switch).
TH146-N-U
Display
Auxiliary
Fan limit
(100 to 194°F)
display
Options
Default
°C / °F
°C
Select the temperature display format.
Set the bP L limit (see section 4.2).
-30 to 10°C
-10°C
NOTE: Lower bP L below its minimum (- -) if you do not wish to use this
(-22 to 50°F)
(14°F)
function.
Set the bP H limit (see section 4.2).
-5 to 30°C
5°C
NOTE: Raise bP H above its maximum (- -) if you do not wish to use this
(23 to 86°F)
(41°F)
function.
Set the defrost point temperature (see section 4.3).
-10 to 15°C
10°C
NOTE: Raise the defrost point above its maximum (- -) if you do not wish to
(14 to 59°F)
(50°F)
use this function.
Set according to the type of heat pump installation (see section 4.4).
Ad (add-on): Use this setting when the indoor coils are located down-
stream of the auxiliary heat source. This is generally the case for add-on
Ad / nr
Ad
installations.
nr (normal): Select this setting when the indoor coils are located
upstream of the auxiliary heat source. This is generally the case for new
installations.
5 to 90 min.
30 min.
Set the interstage delay for the auxiliary stage (see section 4.5).
Set the low temperature limit of the plenum (see section 4.6).
-10 to 20°C
- -
NOTE: This function is not used if you lower LLMT below its minimum (- -)
(14 to 68°F)
or if the plenum temperature sensor is not connected to the controller.
Set the high temperature limit of the plenum (see section 4.6).
30 to 90°C
- -
NOTE: This function is not used if you raise HLMT above its maximum (- -)
(86 to 194°F)
or if the plenum temperature sensor is not connected to the controller.
Select the number of heating/cooling cycles per hour. For optimal heating
control, use the setting that matches your system as follows: 3=20 min (hot
2 to 6
4
water, 90%+ high-efficiency furnace), 4=15 min (gas or oil), 5=12 min (gas
or oil), 6=10 min (electric).
This setting determines the fan operation in automatic mode when the sys-
tem is in heating mode (see section 5.2).
EL (electric heating): The fan starts when heating starts and stops when
heating stops.
GA / EL
EL
GA (gas or oil heating): The fan starts when the temperature inside the
plenum rises above the Fan Limit (see item 11) and stops when the tem-
perature drops 12°C below the Fan Limit. Note: The fan will not start if
the plenum temperature sensor is not connected to the controller.
This parameter is available only when gas heating is selected (see item 10).
WARNING: FLMT can be used in parallel with an UL353-approved
38 to 90°C
80°C
device but they do not replace such device.
(176°F)
NOTE: The fan will not start if you raise FLMT above its maximum (--).
On: Smart Fan is On (see section 4.7).
On / OF
OF
OF: Smart Fan is Off.
0 to 9°C
0°C
Set the amount of temperature setback when the controller is placed in
(0 to 16°F)
(0°F)
Unoccupied mode (see section 5.6).
Select between displaying the outdoor temperature or the indoor humidity
level.
On: Displays the outdoor temperature.
On / OF
On
OF: Displays the indoor humidity level.
NOTE: To display the outdoor temperature, the outdoor sensor must be
connected.
Co (conventional): The humidifier will operate if the humidity is too low. If
the fan is not already On, it will turn On at the same time as the humidi-
fier.
HE (heat): The humidifier can operate only when heating is activated.
Co / HE / Fn
HE
Fn (fan): The humidifier can operate as long as the fan is running,
whether heating is activated or not.
NOTE: The humidifier is disabled when cooling is activated.
Allows you to set the humidity control to automatic mode.
On (automatic): The humidity level is automatically regulated by the con-
troller according to the outdoor temperature to avoid condensation or ice
On / OF
OF
formation on windows while providing enough humidity for your comfort
(see item 17).
OF (manual): The user manually sets the humidity level (see item 17).
Set the desired humidity level. This parameter is available only when the
5 to 60%
5 %
humidity control is placed in manual mode (see item 16).
This parameter is available only when the humidity control is placed in auto-
matic mode (see item 16). It allows the user to apply an offset to the auto-
-9 to 9%
0
matic humidity control. For example, the user can enter a negative offset if
there is ice formation or condensation on the windows.
Description