Auber Instruments SYL-2372 Manuel d'instruction - Page 4

Parcourez en ligne ou téléchargez le pdf Manuel d'instruction pour {nom_de_la_catégorie} Auber Instruments SYL-2372. Auber Instruments SYL-2372 8 pages.

Auber Instruments SYL-2372 Manuel d'instruction
AUBER INSTRUMENTS
Hy-2: Deviation low alarm. If the temperature is below "SV - Hy-2 - Hy", the
alarm will turn on, and the alarm will turn off if the temperature is greater
than "SV - Hy-2 + Hy".
The things you should know about alarms
1) Absolute alarm and deviation alarm
High (or low) limit absolute alarm is set by the specific temperatures that the
alarm will be on. Deviation high (or low) alarm is set by how many degrees
above (or below) the control target temperature (SV) that the alarm will be on.
For example, ALM1 = 1000 ºF, Hy-1 = 5 ºF, Hy = 1, SV = 700 ºF. When the
probe temperature (PV) is above 706, the deviation alarm will turn on. When
the temperature is above 1001 ºF, the process high alarm will turn on. When
SV changes to 600 ºF, the deviation alarm will be changed to 606 but process
high alarm will remain the same. Please see 4.5.2 for details.
2) Alarm Suppression feature
Sometimes, user may not want the low alarm to be turned on when starting the
controller at a temperature below the low alarm setting. The Alarm Suppression
feature will suppress the alarm from turning on when the controller is powered
up (or SV changes). The alarms can only be activated after the PV reaches SV.
This feature is controlled by the B constant of the COOL parameter (see 4.14).
The default setting is alarm suppression on. If you use the AL1 or AL2 relay for
a control application that needs it to be active as soon as the controller is
powered up, you need to turn off the alarm suppression by setting B = 0.
3) Assignment of the relays for the alarms
AL1 and AL2 are the name of the two relays used for alarm output. AL1 is the
alarm relay 1 and AL2 is alarm relay 2. Please do not confuse the relays with
alarm parameter ALM1 (process high alarm) and ALM2 (process low alarm).
AL-P (alarm output definition) is a parameter that allows you to select the
relay(s) to be activated when the alarm set condition is met. Please note that
deviation alarm cannot trigger alarm relay AL1. You can set all four alarms to
activate the one relay (AL1 or AL2), but you can't activate both relays for with
just one alarm.
4) Display of the alarm
When AL1 or AL2 relay is activated, the LED on the upper left will light up. If
you have multiple alarms assigned to a single relay, it should be helpful to
know which alarm is activated. This can be done by setting the E constant in
the AL-P parameter (see 4.13). When E = 0, the bottom display of the
controller will alternately display the SV and the activated alarm parameter.
5) Activate the AL1 and AL2 by time instead of temperature
For the controller with the ramp and soak function (SYL-2372P), AL1 and AL2
can be activated when the process reaches a specific time. This is discussed in
the section 3.7 of "Supplementary Instruction Manual for ramp/soak option.
4.4.2 Hysteresis Band "Hy"
The Hysteresis Band parameter Hy is also referred as Dead Band, or
Differential. This permits protection of the on/off control from high switching
frequency caused by process input fluctuation. Hysteresis Band parameter is
used for on/off control, 4-alarm control, as well as the on/off control at auto
tuning. For example: (1) When the controller is set for on/off heating control
mode, the output will turn off when temperature goes above SV + Hy and on
again when it drops to below SV - Hy. (2) If the high alarm is set at 800 ° F and
hysteresis is set for 2 ° F, the high alarm will be on at 802 ° F (ALM1 + Hy) and
off at 798 ° F (ALM1 - Hy).
Please note that the cycle time can also affect the action. If the temperature
passes the Hy set point right after the start of a cycle, the controller will not
respond to the Hy set point until the next cycle. If cycle time is set to 20
seconds, the action can be delay as long as 20 seconds. Users can reduce the
cycle time to avoid the delay.
4.4.3 Control mode "At"
2021.06
At = 0. on/off control. It works like a mechanical thermostat. It is suitable for
devices that do not like to be switched at high frequency, such as motor and
valves. See 4.5.2 for details.
At = 1. Start auto tuning. In display mode 1, press the A/M key and auto tuning
will initiate.
At = 2. Start auto tuning. It will initiate automatically after 10 seconds. The
function is the same as starting auto tuning from front panel (At = 1).
At = 3. This configuration applies after auto tuning is done. Auto tuning from the
front panel is inhibited to prevent accidental re-starting of the auto tuning
process. To start auto tuning again, set At = 1 or At = 2.
4.5 Control action explanations
4.5.1 PID control mode
Please note that because this controller uses fuzzy logic enhanced PID control
software, the definition of the control constants (P, I and d) are different than
that of the traditional proportional, integral, and derivative parameters. In most
cases the fuzzy logic enhanced PID control is very adaptive and may work well
without changing the initial PID parameters. However, users may need to use
auto-tune function to let the controller determine the parameters automatically.
If the auto tuning results are not satisfactory, you can manually fine-tune the
PID constants for improved performance. Or you can try to modify the initial
PID values and perform auto tune again. Sometimes the controller will get the
better parameters.
The auto-tune can be started in two ways. 1) Set At = 2. It will start
automatically after 10 seconds. 2) Set At = 1. You can start the auto-tune any
time during the normal operation by pressing the A/M key. During auto tuning,
the instrument executes the on-off control. After 2-3 times on-off action, the
microprocessor in the instrument will analyze the period, amplitude, waveform
of the oscillation generated by the on-off control, and calculate the optimal
control parameter value. The instrument begins to perform accurate artificial
intelligence control after auto tuning is finished. If you want to exit from the auto
tuning mode, press and hold the (A/M) key for about 2 seconds until the
blinking of "At" symbol is stopped in the lower display window. Generally, you
will need to perform auto tuning once. After the auto tuning is finished. The
instrument will set parameter "At" to 3, which will prevent the (A/M) key from
triggering auto-tune. This will prevent an accidental repeat of the auto-tuning
process.
(1) Proportional constant "P"
Please note the P constant is not defined as Proportional Band as in the
traditional model. Its unit is not in degrees. A larger constant results in larger
and quicker action, which is the opposite of the traditional proportional band
value. It also functions in the entire control range rather than a limited band.
If you are controlling a very fast response system ( > 1° F/second) that fuzzy
logic is not quick enough to adjust, set P = 1 will change the controller to the
traditional PID system with a moderate gain for the P.
(2) Integral time "I"
Integral action is used to eliminate offset. Larger values lead to slower action.
Increase the integral time when temperature fluctuates regularly (system
oscillating). Decrease it if the controller is taking too long to eliminate the
temperature offset. When I = 0, the system becomes a PD controller.
(3) Derivative time "D"
Derivative action can be used to minimize the temperature over-shoot by
responding to its rate of change. The larger the number, the faster the action.
4.5.2 On/off control mode
It is necessary for inductive loads such as motors, compressors, or solenoid
valves that do not like to take pulsed power to enable the On/Off control mode.
When the temperature passes hysteresis band (Hy), the heater (or cooler) will
be turned off. When the temperature drops back to below the hysteresis band,
the heater will turn on again.
WWW.AUBERINS.COM
P4/8