SPECIFICATIONS

Section 7
7.1

General Technical Data

Mains Supply
Mains voltage (L1, L2, L3)
CSX-xxx-V4 ............................................................................................... 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSX-xxx-V6 ............................................................................................... 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start) .......................................................................................................................................... 45 Hz to 66 Hz
Rated insulation voltage ............................................................................................................................................................ 600 VAC
Form designation ........................................................................................ Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)
CSX-xxx-xx-C1 ............................................................................................................................. 110-240 VAC (+ 10% / - 15%)
..................................................................................................................................................... or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2 ............................................................................................................................................... 24 VAC/VDC (± 20%)
Current consumption (during run) .................................................................................................................................. < 100 mA
Current consumption (inrush)
CSX-xxx-xx-C1 ............................................................................................................................................................................... 10 A
CSX-xxx-xx-C2 .................................................................................................................................................................................. 2 A
Inputs
Start (terminal 01) ........................................................................................................................................................... Normally open
................................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
Stop (terminal 02) ......................................................................................................................................................... Normally closed
................................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
Outputs
Main contactor (terminals 13, 14) ......................................................................................................................... Normally open
............................................................................................................................ 6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Run relay (terminals 23, 24) ...................................................................................................................................... Normally open
............................................................................................................................ 6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Environmental
Degree of protection CSX-007 to CSX-055 .......................................................................................................................... IP20
Degree of protection CSX-075 to CSX-110 .......................................................................................................................... IP00
Operating temperature ....................................................................................................................................... - 10 °C to + 60 °C
Storage temperature ............................................................... -25 °C to + 60 °C (to +70 °C for less than 24 hours)
Humidity ................................................................................................................................................ 5% to 95% Relative Humidity
Pollution degree ....................................................................................................................................................... Pollution Degree 3
Vibration ................................................................................................................................................. IEC 60068 Test Fc Sinusoidal
....................................................................................................................................... 4 Hz to 13.2 Hz: ± 1 mm displacement
.................................................................................................................................................................. 13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC) .............................................................................................................................................................. Class A
Conducted radio frequency emission ................................................................... 0.15 MHz to 0.5 MHz: < 90 dB (µV)
................................................................................................................................................... 0.5 MHz to 5 MHz: < 76 dB (µV)
.................................................................................................................................................. 5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission .................................................................... 30 MHz to 230 MHz: < 30 dB (µV/m)
................................................................................................................................... 230 MHz to 1000 MHz: < 37 dB (µV/m)
1
This product has been designed as Class A equipment. Use of this product in domestic environments may
cause radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic discharge ......................................................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field .............................................................. 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) ............................ 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ...................................................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion ................................................................................... IEC61000-2-4 (Class 3), EN/IEC61800-3