3onedata CAN232 Manuel de l'utilisateur - Page 3

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} 3onedata CAN232. 3onedata CAN232 3 pages. Interface converter
Également pour 3onedata CAN232 : Manuel d'installation rapide (3 pages)

3onedata CAN232 Manuel de l'utilisateur
When the CAN232 converter is used as the CAN-bus network
terminal, the two pin is connected to a resistance of 120Ω,
otherwise no need to install a 120Ω resistor.
Serial port connection
RS-232 side is DB9 Female. The 3-PIN definition is as follows:
PIN
1
2
TxD
DB9 Female
3
RxD
4
5
GND
6/7/8/9

【LED Indicator】

LED indictor light on the top panel of product, the function of
each LED is described in the table as below.
System statue LED
LED
Indicate
Description
ON
Power is connected/Function natural
PWR
Power is disconnected or function
OFF
nu-natural
ON
CAN-Bus port connect successfully
CAN
Flashing
CAN-Bus port has data transmission
OFF
CAN-Bus port connect unsuccessfully
ON
Serial port connect successfully
Flashing
In transmitting/ receiving data
RS-232
OFF
None data receive/ transmit
【Installation】
Before installation, confirm that the work environment meet the
installation require, including the power needs and abundant
space. Whether it is close to the connection equipment and other
equipments are prepared or not.
1. Avoid in the sunshine, keep away from the heat fountainhead or
the area where in intense EMI.
2. Examine the cables and plugs that installation requirements.
3. Power: 9 ~ 48VDC
4. Environment: working temperature: -40~75℃
5. Support wall or DIN-Rail mounted
RS-232
Wiring Requirements
Cable laying need to meet the following requirements,
Transmit data
1. It is needed to check whether the type, quantity and
Received data
specification of cable match the requirement before cable
laying;
Signal ground
2. It is needed to check the cable is damaged or not, factory
records and quality assurance booklet before cable laying;
3. The required cable specification, quantity, direction and
laying position need to match construction requirements, and
cable length depends on actual position;
4. Cables should be straight in the hallways and turning;
5. Cable should be straight in the groove, and cannot beyond the
groove in case of holding back the inlet and outlet holes.
Cables should be banded and fixed when they are out of the
groove;
6. User cable should be separated from the power lines. Cables,
power lines and grounding lines cannot be overlapped and
mixed when they are in the same groove road. When cable is
too long, it cannot hold down other cable, but structure in the
middle of alignment rack;
7. It should have corresponding simple signal at both sides of the
cable for maintaining.
【Specification】
Serial Interface
Standard: RS-232
RS-232 signal: RXD, TXD, GND
Parity bit: None, Even, Odd, Space, Mark
Data bit: 8bit
Storage Temperature: -40~85℃
Relative humidity 5%~95%
- 3 -
Stop bit: 1bit, 2bit
Band rate: 300bps~115200bps
Loading: point to point
Transfer distance: no more than 15m
Connector: DB9 Female
CAN-Bus Interface
Standard: CAN2.0A, CAN2.0B
CAN-Bus signal: CANL, CANH, GND, RES+, RES-
Band rate: 2.5K~1Mbps
Transfer distance: 40m~10Km
Power supply
Input voltage: 9~48VDC
Type of input: 2 bits terminal block
No-load consumption: .0.86W@9VDC
Full-load consumption: 0.89W@9VDC
Power support reverse connection
Working environment
Working temperature: -40~75℃
Storage temperature: -40~85℃
Relative Humidity: 5%~95% (no condensation)
Mechanical Structure
Shell: IP40 protect grade, metal shell
Installation: DIN-Rail or Wall mounting
Weight: 238g
Size (W×H×D): 69mm×22mm×100mm
Industry Standard
EMI: FCC Part 15, CISPR (EN55022) class A
EMS: EN61000-4-2 (ESD), Level 3
Shock: IEC 60068-2-27
Free fall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Certification
CE, FCC, RoHS, UL508 (Pending)
Warranty: 3 years