Duco DucoBox Silent 325 Manuel d'installation - Page 10

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Duco DucoBox Silent 325. Duco DucoBox Silent 325 16 pages.
Également pour Duco DucoBox Silent 325 : Manuel de démarrage rapide (16 pages), Manuel d'installation (12 pages), Manuel d'installation (16 pages)

Duco DucoBox Silent 325 Manuel d'installation
ENGLISH
06.G Tips
• Removing all components from the network (e.g. in the event of problems): Activate 'Installer mode' and long-press 'INST'
until the LED starts flashing red� The DucoBox will reboot (around 15 seconds) and the LED will stop flashing�
• Restore factory settings for the DucoBox and all paired components (AS FROM DucoBox version 18xxxx): Long-press 'INST'
and 'ENTER' if not in 'Installer mode'. The network remains in place�
• Use the Duco Network Tool to read out information from components�

07 Air calibration

The system needs to be configured for it to work correctly� This will ensure its operation is as quiet as possible and energy-efficient�
See under the Tools heading at www�duco�eu for information about determining ventilation flow rates�
07.A Air calibration procedure for DucoBox Silent Connect
The air calibration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling, fee-
ling the wind in one's face)�
Air calibrating the DucoBox Silent Connect
Set all exhaust vents so they match the desired flow rate in accor-
dance with the table below� Proper pre-setting makes for rapid and
correct configuration�
Flow
rate
75m³/h
1
50m³/h
25m³/h
When using DucoVent Design exhaust vents always leave the outer
ring in place for acoustic effect�
Before activating air calibration mode:
• Close all windows and doors�
• Ensure that all duct openings in the DucoBox are fully closed and that the
2
DucoBox cover is closed!
• Avoid air leaks in the ventilation ducts�
• Set all window ventilators to the open position
10
L2000641 Installation guide for DucoBox Silent (Revision G | 17.07.2019)
DucoVent
DucoVent Basic
Design
and other vents
100% open
50% open
25% open
Example
Toilet
Kitchen
Bathroom
Storeroom
open