3onedata GW1114 Series Manuel d'installation rapide - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel d'installation rapide pour {nom_de_la_catégorie} 3onedata GW1114 Series. 3onedata GW1114 Series 3 pages. Modbus gateway

3onedata GW1114 Series Manuel d'installation rapide
5.
Serial port receiving data indicators
6.
Terminal block for power input
7.
Grounding screw
8.
DIP switch
9.
Console Port
10.
100 Base-T(X)
11.
RS-485/422/232 serial port
12.
RS-485/422 serial port
13.
Foot pad
14.
Wall-mounting location hole
【Mounting Dimension】
Unit: mm
Note before mounting:
Don't place or install the device in area near water or
moist, keep the relative humidity of the device
surrounding between 5%~95% without condensation.
Before power on, first confirm the supported power
supply specification to avoid over-voltage damaging the
device.
The device surface temperature is high after running;
please don't directly contact to avoid scalding.
【Wall-mounted Device Mounting】
Step 1
Adopt M3 screw to install the left/right mounting
board on the device backboard.
Step 2
Place the device on the wall as reference or
reference installation dimension; mark 2 bolt
positions on the wall.
Step 3
Nail M4 screws on the wall and keep 2mm
interspace reserved.
Step 4
Hang the device on two screws and slide
downward, then tighten the screw to enhance
stability, mounting ends.
【Wall-mounted Device Disassembling】
Step 1
Device power off.
Step 2
Unscrew the screw on the wall about 2mm.
Step 3
Lift the device upward slightly; take out the device,
disassembling ends.
Note before powering on:
Power ON operation: First insert the power supply
terminal block into the device power supply interface,
and then plug the power supply plug contact and power
on.
Power OFF operation: first unpin the power plug, then
remove the power line, please note the operation order
above.
【Power Supply Connection】
DC power supply
This device provides 3-Pin 5.08mm pitch terminal
blocks, in which V+ and V- are DC input, FG is the
power grounding input; The power supply
supports non-polarity, power supply range: 12~48VDC
【DIP Switch Settings】
Provide 4 pins DIP switch for function settings,
where "ON" is enable valid terminal. The device
needs to be powered on again to change the status of DIP
switch.
DIP switches definition as follows:
DIP
Definition
Operation
1
Reserved
-
2
Restore factory
Set the DIP switch to ON,
defaults
power on the device again, it
will restore to factory settings,
then turn off the DIP switch.
3
Reserved
-
4
Reserved
-
【Serial Port Connection】
3IN1 Interface
The model I of this series provides 3IN1 serial port, which
supports RS232, RS485 and RS422 at the
same time. The interface type is RJ45 and its
pin definitions are as follows:
1
2
3
4
PIN
RS-232 DSR RTS GND TXD RXD DCD CTS DTR
RS-485 —
GND —
RS-422 —
R-
GND R+
RS-485/ 422 interface
.
5.
6
7
8
D-
D+
T-
T+