Danfoss DEVIreg 532 Manuel d'installation - Page 7

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Danfoss DEVIreg 532. Danfoss DEVIreg 532 16 pages. Electronic thermostat

DEVIreg™ 532
• Place the floor sensor in a conduit in an appropriate
place where it is not exposed to sunlight or draft from
door openings.
• Equally distant and >2cm from two heating cables.
• The conduit should be flush with the floor surface -
countersink the conduit if necessary.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min 50mm.
Installation Guide
Always install the thermostat at least 50 cm.
from windows and doors.
Do not place the thermostat in a way that
it will be exposed to direct sunlight.
Note: A floor sensor enables a more accurate
temperature control and is recommended
in all floor heating applications
and mandatory under wooden floors to
reduce the risk of over-heating the floor.
7