Danfoss ECL Comfort 296 Manuel d'utilisation - Page 10

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Danfoss ECL Comfort 296. Danfoss ECL Comfort 296 16 pages. Return temperature limitation
Également pour Danfoss ECL Comfort 296 : Manuel de l'utilisateur (12 pages), Manuel d'installation (20 pages), Manuel d'entretien (16 pages), Manuel d'utilisation (8 pages), Manuel d'utilisation (10 pages), Manuel d'installation (16 pages), Manuel d'installation (16 pages), Manuel d'installation (16 pages), Manuel d'installation (20 pages), Manuel d'installation (12 pages), Manuel d'installation (16 pages), Manuel d'utilisation (8 pages)

Danfoss ECL Comfort 296 Manuel d'utilisation
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
Ramp X5 - X6 (Temperature ramping from time X5
to X6)
Ramp X7 - X8 (Temperature ramping from time X7
to X8)
Setting the number of steps for the change of the desired flow
temperature in selected period.
OFF:
The stepwise change is disabled
Value: The period is divided in the number of steps
Example:
"X5" time is set to 100
"X5" temperature is set to 25 °C
"X6" time is set to 150
"X6" temperature is set to 35 °C
"Ramp X5 - X6" is set to 5
Result:
Period between X5 and X6 is 50 hours. Temperature change is 10 K.
The process will be:
Start temperature: 25 °C, after 10 hours the temperature changes
to 27 °C. After further 10 hours the temperature changes to 29 °C
and so on.
Appl. continue (Application continue)
Selection how the ECL Comfort controller must continue after
having finished the floor drying process.
OFF:
The desired flow temperature will be the value set at
"X8" time
ON:
The controller continues with the selected application
and the set mode of the function selector
After power fail. (After power failure)
Selection how the ECL Comfort controller must continue after a
power failure (power has been away for more than accepted time,
set in "Max. pwr. failure", ID 10514).
If power failure happens in "Functional heating" process, the floor
drying can be restarted according to time and temperature setting
for X1 or stopped. If stopped, the desired flow temperature is
maintained at the value, set for X1.
If power failure happens in "Curing heating" process, the floor
drying can be restarted according to time and temperature setting
for X4. If stopped the desired flow temperature is maintained at
the value, set for X1.
STOP:
The controller stops the floor drying process and
maintains the temperature, set at X1
START: The controller starts the floor drying process from
settings in X1 or X4
To restart the floor drying process:
If the parameter "After power fail." (ID 10913) is set to STOP, the
"Prog. execution" must be set to OFF and then to ON.
10 | © Danfoss | 2017.08
10903
10904
10912
When using only "Functional heating" and no demand for control after
the floor drying process, it is important to set the desired temperature
at X8.
(Common controller > MENU > Floor drying > Curing heating >
"Desired flow T" > Graph's right point).
10913
After a power failure, the alarm is indicated.
The alarm can be reset.
VI.JM.P2.02