Adjustment spindles location
Note!
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
See printed instruction on top of control
increase temp. (warmer): turn CW
decrease temp. (colder): turn CCW
(use adjustment knob)
Determination of diff erential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct diff erential
Example:
HSP = +45°F (+5.6°C)
=>
LSP = +32°F (0°C
© Danfoss A/S
DIFF (from graph):
13°F (7.2°C) (value which has to be
set on diff . scale).
RI.5D.A2.22 → DKRCC.PI.C0A.A1.22-520H2749
DIFFERENTIAL
See printed instruction on top of control
Increase: turn CW
decrease: turn CCW
(use adjustment knob or screwdriver)
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The diff erential will be HSP less LSP
Example:
HSP – LSP = DIFF.
45°F – 35°F = 10°F
(7°C)
(5°C)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
CUT-OUT = LSP
CUT-OUT = HSP
See "Wiring"
(2°C)
= LSP