Danfoss Type CFR Manuel de l'utilisateur - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} Danfoss Type CFR. Danfoss Type CFR 2 pages. Room thermostat
Room Thermostat
Instructions for Installation
088R0228
DKCD 03/01
Type CFR
1
2
Registration field in
CFM
3
Each room thermostat has a unique ID number
preventing conflicts with other thermostats. A single
room thermostat is capable of regulating several
heating outputs, provided these outputs are assigned to
the thermostat.
Assigning thermostats to output(s)
-The installation cable between room thermostat and
CFM (fig. 1) must be connected in assigning each
thermostat to the respective output(s).
-In the LED array the first available position will flash.
Outputs already assigned will not be lit (fig. 2). By
pressing OK the thermostat will be assigned to that
output. If the room thermostat is to be assigned under
another lit output, scroll to the output by means of the +/-
keys, then press OK.
-When the installation cable is removed, the red LED
underneath the battery cover (fig. 1) will flash for at
least one minute (Test mode).
Removal of assigned thermostat
-It is not necessary to have the installation cable in
place when removing an assigned thermostat. Once a
thermostat has been removed, it may be reassigned to
another output.
-Removal of room thermostat is done by pressing OK
for 5 seconds, then the entire LED array will be lit.
Scroll to the specific room thermostat to be removed
with the +/- button,and press OK for 5 seconds. The
thermostat has now been removed.
Test of room thermostat
If a defect in a room thermostat is suspected, the fol-
lowing test may be carried out:
- Set the thermostat to the highest temperature.
- Move the function switch on the side of the room ther-
mostat to a new position.
- If the LED underneath the battery cover (fig. 1) flashes
quickly for 3 minutes, the room thermostat is OK.