Danfoss E4h Manuel d'installation - Page 7

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Danfoss E4h. Danfoss E4h 8 pages. Igbt module replacement for frequency converters and drives
Également pour Danfoss E4h : Instructions d'installation (4 pages)

Danfoss E4h Manuel d'installation
IGBT Module Replacement for Fx09-Fx12 and E1h–E4h
Installation Guide
Kit number
Mounting torque
[Nm (in-lb)]
176F3957
4.5 (40)
176F3946
3.3 (29)
176F4012
4.5 (40)
Table 8: Torque Tightening Values and Sequence for VLT
Kit number
Mounting torque
[Nm (in-lb)]
176F6641
3.3 (29)
176F6642
4.5 (40)
176F6643
3.3 (29)
176F6644
4.5 (40)
176F6711
3.3 (29)
176F6646
4.5 (40)
Danfoss A/S © 2022.03
Busbar connection
Diagram
torque [Nm (in-lb)]
9.0 (80)
B
3.3 (29)
A
9.0 (80)
B
®
FC Series Drives
Busbar connection
Diagram
torque [Nm (in-lb)]
4.0 (35)
A
9.0 (80)
B
4.0 (35)
A
9.0 (80)
B
4.0 (35)
A
9.0 (80)
B
Installation
Screw tightening order
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
Screw tightening order
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
AN361427984575en-000101 / 130R0770 | 7