Danfoss 176F4060 Manuel d'installation - Page 11

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Danfoss 176F4060. Danfoss 176F4060 16 pages. In-bottom/out-back cooling kit for fa11-fa12, frequency converters

Danfoss 176F4060 Manuel d'installation
In-bottom/Out-back Cooling Kit for FA11-FA12
Installation Guide
3.
With the rubber seal in place, carefully slide the inner sleeve of the duct into the outer sleeve.
1
2
3
Illustration 9: Assembly of Telescopic Duct
1
Inner sleeve of duct
2
Ribbed EPDM rubber seal
2.7 Installing the Duct Support Bracket
The duct support bracket attaches the bottom duct to the lower end of the cooling back channel. To install the bracket, use the
following steps. Refer to
Illustration
Procedure
1.
Remove the paper backing from the duct support gasket.
2.
Adhere the gasket to the upper surface of the duct support bracket.
3.
Position the bracket at the lower end of the cooling back channel.
4.
Secure the bracket to the back channel of the frequency converter using 8 M5x14 screws (T25) from the kit.
Torque fasteners to 2.3 Nm (20 in-lb).
Danfoss A/S © 2022.12
10.
3
Outer sleeve of duct
AN361429392581en-000201 / 136R0253 | 11
Installation