Danfoss VLT 5000 Manuel - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Danfoss VLT 5000. Danfoss VLT 5000 7 pages. Frequency converter
Également pour Danfoss VLT 5000 : Note d'application (16 pages)
Configuring of the CMD and VLT 5000
The first step is to connect all Interbus slaves to the
master and power up all units.
Start the IBS CMD software and choose a new
project from File and New.
The screen should now look like this:
Next step is to read the slaves on the bus system.
Click on Configuration frame and click on the right
mouse button. Select Read In and choose Startup
without PDP.
The state will be changed from Offline to Online
when the Read In is finished. Please look at the
bottom of the screen.
After the Read In, CMD will indicate each VLT
frequency converter with a DriveCom symbol, a
station number and an ID number.
2
®
VLT
5000 and Interbus CMD
Next step is to configuring the Interbus system. This
is done by clicking on the VLT symbol and pressing
the right mouse button. Select Description.
Here you can type a Station name, Device name
and a Device number.
Click on Parameter Channel.
By message lenght transmit and receive enter 246
Byte and select Get-OD (long format). The message
length now corresponds to the internal buffer in the
VLT frequency converter. Get-OD (long format)
means that the master will read the English
parameter description text from the VLT frequency
converter.
Press OK twice.
MN.50.U1.02 - VLT is a registered Danfoss trademark